Endress+Hauser Prosonic M FMU42 HART Operating Instructions Manual

Endress+Hauser Prosonic M FMU42 HART Operating Instructions Manual

Ultrasonic measuring technology
Hide thumbs Also See for Prosonic M FMU42 HART:
Table of Contents

Advertisement

Quick Links

BA01963F/00/EN/01.22-00
71574096
2022-04-04
Products
Operating Instructions
Prosonic M FMU42
HART
Ultrasonic measuring technology
Solutions
Services

Advertisement

Table of Contents
loading

Summary of Contents for Endress+Hauser Prosonic M FMU42 HART

  • Page 1 Products Solutions Services BA01963F/00/EN/01.22-00 71574096 2022-04-04 Operating Instructions Prosonic M FMU42 HART Ultrasonic measuring technology...
  • Page 2 Prosonic M FMU42 HART Order code: XXXXX-XXXXXX Ser. no.: XXXXXXXXXXXX Ext. ord. cd.: XXX.XXXX.XX Serial number www.endress.com/deviceviewer Endress+Hauser Operations App A0023555 Endress+Hauser...
  • Page 3: Table Of Contents

    Manufacturer address ....8 12.2 Endress+Hauser services ....40 Storage and transport .
  • Page 4: About This Document

    About this document Prosonic M FMU42 HART About this document Document function These Operating Instructions provide all of the information that is required in the various phases of the life cycle of the device. Symbols 1.2.1 Safety symbols DANGER This symbol alerts you to a dangerous situation. Failure to avoid this situation will result in serious or fatal injury.
  • Page 5: Supplementary Documentation

    For an overview of the scope of the associated Technical Documentation, refer to the following: • W@M Device Viewer (www.endress.com/deviceviewer): Enter serial number from nameplate • Endress+Hauser Operations app: Enter serial number from nameplate. 1.3.1 Standard documentation Technical Information (TI) Planning aid ‒...
  • Page 6: Basic Safety Instructions

    The device meets the legal requirements of the applicable EU Directives. These are listed in the corresponding EU Declaration of Conformity along with the standards applied. Endress+Hauser confirms successful testing of the device by affixing to it the CE mark. Endress+Hauser...
  • Page 7: It Security

    The device meets the legal requirements of the applicable EAC Directives. These are listed in the corresponding EAC Declaration of Conformity along with the standards applied. Endress+Hauser confirms successful testing of the device by affixing to it the EAC mark. IT security We only provide a warranty if the device is installed and used as described in the Operating Instructions.
  • Page 8: Incoming Acceptance And Product

    ‣ Enter the serial number from the nameplate in the Endress+Hauser Operations app or scan the 2-D matrix code on the nameplate with the camera  All of the information on the measuring device and on the scope of the technical documentation pertaining to the device is displayed.
  • Page 9: Storage And Transport

    Prosonic M FMU42 HART Mounting Place of manufacture: See nameplate. Storage and transport • Pack the measuring device so that it is protected against impact. The original packaging offers the best protection • Permitted storage temperature: –40 to +80 °C (–40 to 176 °F) 4.4.1...
  • Page 10 Mounting Prosonic M FMU42 HART • Only mount one device per vessel: signals from multiple devices mutually affect one another • Determine the detection range using the 3-dB beam angle α 5.1.2 Beam angle W = 2 · D · tan A0038221 ...
  • Page 11 Prosonic M FMU42 HART Mounting 5.1.4 Installation conditions for the sensor for flow measurements • Mount the measuring device on the upstream side immediately above the maximum upper water level H • Take the blocking distance into account • Position the measuring device in the center of the flume or weir •...
  • Page 12 Mounting Prosonic M FMU42 HART ≥3 H ≥ 2 H A0038223  8 Triangular weir (example) BD Blocking distance of the sensor Empty calibration (enter during commissioning) Full calibration Maximum upstream level 5.1.5 Mounting examples A0038822  9 Mounting examples Mounting with universal flange (e.g.
  • Page 13: Measuring Range

    Prosonic M FMU42 HART Mounting 5.1.6 Turning the housing 4 mm A0037777  10 Turning the F12 or T12 housing, (F12 housing in example) 1. Loosen the securing screw. 2. Rotate the housing in the desired direction, maximum 350 °.
  • Page 14 Mounting Prosonic M FMU42 HART A0038238  11 Parameter for the correct operation of the device BD Blocking distance Safety distance Empty calibration Measuring span Mounting nozzle A0038371  12 Definition of nozzle length L and nozzle diameter D Nozzle diameter...
  • Page 15: Post-Mounting Check

    Prosonic M FMU42 HART Electrical connection 5.2.3 Safety distance The device generates a warning or alarm if the level reaches the safety distance (SD). The SD size can be set as required by the user in the Safety distance (015) function.
  • Page 16: Connecting The Measuring Device

    Electrical connection Prosonic M FMU42 HART Connecting the measuring device 6.2.1 Connection in the F12 housing 1 → 2 → 3 → A0038240 A0038241 A0038242 ‣ ‣ ‣ Unscrew the cover Remove the display if one is Remove the cable from the...
  • Page 17: Terminal Assignment

    Prosonic M FMU42 HART Electrical connection 6.2.2 Connection in the T12 housing 1 → 2 → 3 → A0038256 A0038257 A0038258 ‣ ‣ Unscrew the cover Avoid moisture in the housing, provide a loop to allow moisture to drain off 4 →...
  • Page 18: Supply Voltage

    Electrical connection Prosonic M FMU42 HART ‣ A standard device cable suffices if only the analog signal should be used. Use a shielded cable if working with a superimposed communication signal (HART). Protective circuits against reverse polarity, RF influences and overvoltage peaks are integrated in the device.
  • Page 19: Post-Connection Check

    Prosonic M FMU42 HART Operation options A0038292  14 Position of outer ground terminal, example of F12 housing • Connect the potential equalization line to the outer ground terminal of the transmitter • In the case of hazardous area applications, only ground on the sensor side •...
  • Page 20: Access To The Operating Menu Via The Local Display

    Operation options Prosonic M FMU42 HART The first two digits identify the function group, examples: • Basic setup: 00 • Safety settings: 01 • Linearization: 04 The third digit refers to the individual functions within the function group, examples: • Tank shape: 002 •...
  • Page 21 Prosonic M FMU42 HART Operation options A0047446  18 Envelope curve display Envelope curve, view Symbols ALARM_SYMBOL The device is in an alarm state. If the symbol flashes, this indicates a warning. LOCK_SYMBOL Device is locked. Additional entries are not possible.
  • Page 22: Access To The Operating Menu Via The Operating Tool

    Operation options Prosonic M FMU42 HART 7.3.2 Operating the local display Group selection 1. Press   Change from the Measured value display to the Group selection. 2. Press  or : select the Function group. 3. Press : confirm your choice.
  • Page 23: Locking Or Enabling Parameter Configuration

    Operating Instructions BA00060S/04. 8.1.2 Operation with FieldCare FieldCare is an Endress+Hauser asset management tool based on FDT technology. FieldCare configures all Endress+Hauser devices and devices from other manufacturers that support the FDT standard. Hardware and software requirements: www.de.endress.com - Search: FieldCare FieldCare supports the following functions: •...
  • Page 24 System integration Prosonic M FMU42 HART Connection options: • HART via Commubox FXA195 and the USB port on a computer • Commubox FXA291 with ToF Adapter FXA291 via service interface Menu-guided commissioning  20 View in the FieldCare operating program •...
  • Page 25: Commissioning

    Prosonic M FMU42 HART Commissioning Commissioning The Commissioning section contains the following steps: • Function check • Switching on the measuring device • Establishing a connection via Fieldcare • Configuring the measuring device • Displaying the envelope curve Function check 9.1.1...
  • Page 26: Connecting Via Fieldcare

    Commissioning Prosonic M FMU42 HART Parameters that need to be configured when the device is switched on for the first time: • Language Select the language of the display. • Length unit Select the unit of length in which the distance is measured.
  • Page 27 Prosonic M FMU42 HART Commissioning Configuration of the measuring point Tank shape function (002) Selection A0038388  23 Options in the "Tank shape" function Dome ceiling Horizontal cyl Bypass or stilling well/ultrasound guide pipe No ceiling, e.g. dumps, open levels, basins, flume...
  • Page 28 Commissioning Prosonic M FMU42 HART A0038402  24 Some of the options in the "Process cond." function Calm surface Turb. surface Add. agitator Fast change Standard solid Solid dusty Conveyor belt Not in graphic: Standard liq. and Test: no filter Description of options •...
  • Page 29 Prosonic M FMU42 HART Commissioning • Solid dusty • For dusty bulk solids • The filters are set in such a way that even relatively weak wanted signals are detected • Conveyor belt • For bulk solids with rapid changes in the level, e.g. conveyor belts •...
  • Page 30 Commissioning Prosonic M FMU42 HART NOTICE If the blocking distance is undershot, this may cause a device malfunction. ‣ Mount the measuring device high enough that the blocking distance is not reached at the maximum fill level. ‣ Define the safety distance (SD).
  • Page 31: Displaying The Envelope Curve

    Prosonic M FMU42 HART Commissioning Range of mapping (052) function • The range of mapping is displayed, confirm the proposed value or enter your own value • The sensor membrane is always the reference point • The value can be edited by the user •...
  • Page 32 Commissioning Prosonic M FMU42 HART 9.5.3 Envelope curve display (0E3) function If cyclic envelope curve display is active on the display, the measured value is updated at a slower cycle time. Recommendation: exit the envelope curve display after optimizing the measuring point. Press  (the device does not leave the envelope curve display automatically.)
  • Page 33 Prosonic M FMU42 HART Commissioning Activating the horizontal zoom mode 1. Press  or .  is displayed. 2.  increases the horizontal scale. 3.  reduces the horizontal scale. Activating the move mode 1. Then press .  is displayed.
  • Page 34: Diagnostics And Troubleshooting

    Diagnostics and troubleshooting Prosonic M FMU42 HART Diagnostics and troubleshooting 10.1 Present error Display • Error symbol in Measured value display (000) • Diagnostics (0A) function group, Present error (0A0) function • The error with the highest priority is displayed.
  • Page 35: Application Errors

    Prosonic M FMU42 HART Diagnostics and troubleshooting A512 = Recording of mapping Alarm ends after a few seconds A521 = New sensor type identified Perform a reset A671 = Linearization not complete, not usable Perform the basic setup E281 = Wire breakage at temperature sensor...
  • Page 36 Diagnostics and troubleshooting Prosonic M FMU42 HART 2. Check the linearization and correct it: Level/ullage (040), Max. scale (046), Diameter vessel (047), Linearization table. Error: Measured value (000) and measured distance in Distance (008) incorrect. Example: 100% t → A0038459...
  • Page 37 Prosonic M FMU42 HART Diagnostics and troubleshooting 100% t → A0038461 Expected result Error occurred 100% t → A0038462 Expected result Error occurred 1. Perform interference echo suppression (mapping). 2. In the Process cond. (004) function, select "Turb. surface" or "Add. agitator".
  • Page 38: Resetting The Measuring Device

    Diagnostics and troubleshooting Prosonic M FMU42 HART 100% E641 t → A0038464 Expected result Error occurred 1. Check application parameters (002), (003) and (004). 2. Select another installation position. 3. Select a larger sensor. 4. Align the sensor so that it is parallel to the surface of the product, particularly for bulk solids applications.
  • Page 39: Firmware History

    Prosonic M FMU42 HART Maintenance Selection • Delete: delete (reset) an existing interference echo suppression • Inactive: switch off interference echo suppression, mapping is saved • Active: switch interference echo suppression back on 10.7 Firmware history V01.02.00 (01.2002) / V01.02.02 (03.2003) •...
  • Page 40: Repair

    WARNING Incorrect repair can compromise electrical safety! Explosion Hazard! ‣ Only specialist personnel or the Endress+Hauser service team may carry out repairs on Ex-certified devices. ‣ Relevant standards and national regulations on hazardous areas, safety instructions and certificates must be observed.
  • Page 41: Disposal

    Prosonic M FMU42 HART Accessories 12.3 Disposal If required by the Directive 2012/19/EU on waste electrical and electronic equipment (WEEE), the product is marked with the depicted symbol in order to minimize the disposal of WEEE as unsorted municipal waste. Do not dispose of products bearing this marking as unsorted municipal waste.
  • Page 42: Communication-Specific Accessories

    Accessories Prosonic M FMU42 HART Materials • Housing, cover: AlSi12, Screw: V2A • Ground terminal: CuZn nickel-plated Screw: V2A • Display: glass • Cable gland: CuZn nickel-plated • Cable: PVC • Mounting bracket: 316 Ti (1.4571) or 316 L (1.4435) or 316 (1.4401) •...
  • Page 43 The parameters are recorded and transmitted using Fieldgate FXA42, FXA30 and FXA30B gateway types. SupplyCare Hosting is offered as a hosting service (Software as a Service, SaaS). In the Endress+Hauser portal, the user is provided with the data over the Internet.
  • Page 44: Technical Data

    Technical data Prosonic M FMU42 HART Order number: 71274336 For details, see "Technical Information" TI01297S and Operating Instructions BA01778S. Technical data 14.1 Input 14.1.1 Measured variable Distance D between sensor membrane and product surface Using the linearization function, the device uses D to calculate the following in any unit: •...
  • Page 45: Output Signal

    Prosonic M FMU42 HART Technical data 14.2 Output signal 4 to 20 mA with HART 14.2.1 Signal on alarm Call up failure information: • Local display (error symbol, error code and plain text description) • Current output, failure mode can be selected, e.g. according to NAMUR Recommendation NE43 •...
  • Page 46: Performance Characteristics

    Technical data Prosonic M FMU42 HART 14.3.5 HART noise 500 Hz to 10 kHz: U = 2.2 mV (at 500 Ω) 14.4 Performance characteristics 14.4.1 Reference operating conditions • Temperature: +20 °C (+68 °F) • Pressure: 1 013 mbar abs. (15 psi abs.) •...
  • Page 47: Environment

    Prosonic M FMU42 HART Technical data Accuracy impacted: high vapor pressures or outgassing from media, e.g.: • Ethanol • Acetone • Ammonia Please contact the sales organization if the accuracy is affected. 14.5 Environment 14.5.1 Ambient temperature range –40 to +80 °C (–40 to +176 °F) The functionality of the LCD display is limited at Tu < –20 °C (–4 °F) and Tu > ...
  • Page 48: Appendix

    Appendix Prosonic M FMU42 HART 14.6.2 Process pressure range 0.7 to 2.5 bar abs. (10.15 to 36.25 psi) Appendix 15.1 Overview of the operating menu Function groups and functions Basic setup 00 • Tank shape: 002 • Medium property: 003 • Process cond. 004 •...
  • Page 49 Prosonic M FMU42 HART Appendix Output 06 • Commun. address 060 • No. of preambles 061 • Low output limit 062 • Current output mode 063 • Fixed current 064 • Simulation 065 • Simulation value 066 • Output current 067 •...
  • Page 50: Index

    Index Prosonic M FMU42 HART Index Symbols Flow measurement ......11 Full calibration ......29 "Check distance"...
  • Page 51 Prosonic M FMU42 HART Index Range of mapping (052) function ....31 Recording curve ......31 Registered trademarks Trademarks .
  • Page 52 *71574096* 71574096 www.addresses.endress.com...