Start Up

Drive Setup Procedure
The illustration below shows the basic setup procedure. Each step is explained more detailed
on the following pages.
YASKAWA ELECTRIC TOEP C710606 15E - AC Drive V1000 - Quick Start Guide
Install and wire the drive as explained.
Turn the power on.
Initialize the drive if necessary using parameter A1-03.
Set the control mode.
Select Normal / Heavy Duty
Perform Auto-Tuning or set the motor data manually.
Set/check the basic parameters:
b1-01, b1-02 for frequency reference and RUN command source
H1-
, H2-
, H3-
, H4-
Frequency reference values
C1-
, C2-
for Acceleration/Deceleration times and S-curves
Run the motor without load, check the operation and verify, if the
upper controller (e.g. PLC,...) commands to the drive work as
desired.
Connect the load, run the motor and check the operation
Fine tune and set application parameters (e.g. PID,...) if necessary.
Final check the operation and verify the settings.
Drive is ready to run the application
START
, H6-
to configure the I/Os
5 Start Up
EN 23