1 Safety Instructions and General Warnings
Do not remove covers or touch circuit boards while the power is on.
Failure to comply could result in death or serious injury.
Make sure the protective earthing conductor complies with technical standards
and local safety regulations.
The leakage current of this drive exceeds 3.5 mA. Therefore, according to IEC/EN
61800-5-1, automatic power supply interruption in case of discontinuity of the
protective earthing conductor must be provided or a protective earthing conductor with a
cross section of at least 10 mm
Use appropriate equipment for residual current monitoring/detection (RCM/
RCD).
This drive can cause a residual current with a DC component in the protective earthing
conductor. Where a residual current operated protective or monitoring device is used for
protection in case of direct or indirect contact, always use an RCM or RCD of type B
according to IEC/EN 60755.
Always ground the motor-side grounding terminal.
Improper equipment grounding could result in death or serious injury by contacting the
motor case.
Do not perform work on the drive while wearing loose clothing, jewelry or without
eye protection.
Failure to comply could result in death or serious injury.
Remove all metal objects such as watches and rings, secure loose clothing, and wear eye
protection before beginning work on the drive.
Never short the output circuits of the drive.
Do not short the output circuits of the drive. Failure to comply could result in death or
serious injury.
EN 6
W ARNING
(Cu) or 16 mm
(Al) must be used.
2
2
YASKAWA ELECTRIC TOEP C710606 15E - AC Drive V1000 - Quick Start Guide