3 Electrical Installation
EMC Filter Type
Model
CIMR-V
4A0018
4A0023
4A0031
4A0038
Input Fuse Selection
Use the fuses listed in the table on
Control Circuit
The control terminal board is equipped with screwless terminals. Always use wires within
the specification listed below. For safe wiring it is recommended to use solid wires or
flexible wires with ferrules. The stripping length respectively ferrule length should be 8 mm.
EMC Filter Installation
This drive has been tested in accordance with European standards IEC/EN 61800-3. In order
to comply to the EMC standards, wire the main circuit as described below.
1.
Install an appropriate EMC noise filter to the input side. See the list above or refer to
the Technical Manual for details.
2.
Place the drive and EMC noise filter in the same enclosure.
3.
Use braided shield cable for the drive and motor wiring
4.
Remove any paint or dirt from ground connections for minimal ground impedance
5.
Install an AC reactor at drives smaller than 1 kW for compliance with the
IEC/EN 61000-3-2. Refer to the Technical Manual or contact your supplier for
details
EN 16
Motor cable
Schaffner
FS23639-30-07
FS23639-30-07
FS23639-50-07
FS23639-50-07
page 40
Wire Type
Solid
Flexible
Flexible with ferrule
YASKAWA ELECTRIC TOEP C710606 15E - AC Drive V1000 - Quick Start Guide
Main Circuit Terminal Sizes
Recomm.
R/L1, S/L2, T/L3, U/T1,
[mm²]
V/T2, W/T3, - , +1, +2
2.5
4
6
6
when wiring the main circuit.
Wire size (mm
0.2 to 1.5
0.2 to 1.0
0.25 to 0.5
B1, B2
M4
M4
M4
M4
M5
M5
M5
M5
2
)
GND
M5
M5
M6
M6