Download Print this page

YASKAWA CIMR-V BA0001B Quick Start Manual page 40

Compact vector control drive v1000 series; cimr-vc type

Advertisement

8 Instructions for UL and cUL
Wire Gauge
mm
2
(AWG)
8 (8)
14 (6)
22 (4)
30/38 (3/2)
Note: Use crimp insulated terminals or insulated tubing for wiring these connections. Wires should have a
continuous maximum allowable temperature of 75C 600 V UL approved vinyl sheathed insulation.
Ambient temperature should not exceed 30C.
Input Fuse Selection
Branch circuit protection shall be provided by any of the following:
• Non-time delay Class J, T, or CC fuses sized at 300% of the drive input rating
Note: Exceptional models are A6T6 with 2A0002, A6T15 with 2A0004 or 4A0004, A6T20 with 4A0005,
and A6T25 with 4A0007.
• Time delay Class J, T, or CC fuses sized at 175% of the drive input rating
• Time-delay Class RK5 fuses sized at 225% of the drive input rating
Non-Time Delay
Model
Class-T Fuse Type
CIMR-V
(Manufacturer: Ferraz)
BA0001
BA0002
BA0003
BA0006
BA0010
BA0012
BA0018
2A0001
2A0002
2A0004
EN 40
Terminal Screws
M4
M5
M6
M8
M4
M5
M6
M8
M6
M8
M8
Fuse Ampere
Rating (A)
Single-Phase 200 V Class
A6T6
A6T10
A6T20
A6T40
A6T40
A6T50
A6T80
Three-Phase 200 V Class
A6T3
A6T6
A6T15
YASKAWA ELECTRIC TOEP C710606 15E - AC Drive V1000 - Quick Start Guide
Crimp Terminal
Model Number
8-4
R8-5
R8-6
R8-8
14-4
R14-5
R14-6
R14-8
R22-6
R22-8
R38-8
Fuse Type
(Manufacturer:
Bussmann)
500 Vac, 200 kAIR
6
FWH-25A14F
10
FWH-25A14F
20
FWH-60B
40
FWH-80B
40
FWH-100B
50
FWH-125B
80
FWH-175B
3
FWH-25A14F
6
FWH-25A14F
15
FWH-25A14F
Tightening Torque
Nm (lbin.)
1.2 to 1.5 (10.6 to 13.3)
2.0 to 2.5 (17.7 to 22.1)
5.4 to 6.0 (47.8 to 53.1)
9.9 to 11.0 (87.6 to 97.4)
1.2 to 1.5 (10.6 to 13.3)
2.0 to 2.5 (17.7 to 22.1)
5.4 to 6.0 (47.8 to 53.1)
9.9 to 11.0 (87.6 to 97.4)
5.4 to 6.0 (47.8 to 53.1)
9.9 to 11.0 (87.6 to 97.4)
9.9 to 11.0 (87.6 to 97.4)
Fuse Ampere
Rating (A)
25
25
60
80
100
125
175
25
25
25

Advertisement