8 Instructions for UL and cUL
Wire Gauge
mm
2
(AWG)
8 (8)
14 (6)
22 (4)
30/38 (3/2)
Note: Use crimp insulated terminals or insulated tubing for wiring these connections. Wires should have a
continuous maximum allowable temperature of 75C 600 V UL approved vinyl sheathed insulation.
Ambient temperature should not exceed 30C.
Input Fuse Selection
Branch circuit protection shall be provided by any of the following:
• Non-time delay Class J, T, or CC fuses sized at 300% of the drive input rating
Note: Exceptional models are A6T6 with 2A0002, A6T15 with 2A0004 or 4A0004, A6T20 with 4A0005,
and A6T25 with 4A0007.
• Time delay Class J, T, or CC fuses sized at 175% of the drive input rating
• Time-delay Class RK5 fuses sized at 225% of the drive input rating
Non-Time Delay
Model
Class-T Fuse Type
CIMR-V
(Manufacturer: Ferraz)
BA0001
BA0002
BA0003
BA0006
BA0010
BA0012
BA0018
2A0001
2A0002
2A0004
EN 40
Terminal Screws
M4
M5
M6
M8
M4
M5
M6
M8
M6
M8
M8
Fuse Ampere
Rating (A)
Single-Phase 200 V Class
A6T6
A6T10
A6T20
A6T40
A6T40
A6T50
A6T80
Three-Phase 200 V Class
A6T3
A6T6
A6T15
YASKAWA ELECTRIC TOEP C710606 15E - AC Drive V1000 - Quick Start Guide
Crimp Terminal
Model Number
8-4
R8-5
R8-6
R8-8
14-4
R14-5
R14-6
R14-8
R22-6
R22-8
R38-8
Fuse Type
(Manufacturer:
Bussmann)
500 Vac, 200 kAIR
6
FWH-25A14F
10
FWH-25A14F
20
FWH-60B
40
FWH-80B
40
FWH-100B
50
FWH-125B
80
FWH-175B
3
FWH-25A14F
6
FWH-25A14F
15
FWH-25A14F
Tightening Torque
Nm (lbin.)
1.2 to 1.5 (10.6 to 13.3)
2.0 to 2.5 (17.7 to 22.1)
5.4 to 6.0 (47.8 to 53.1)
9.9 to 11.0 (87.6 to 97.4)
1.2 to 1.5 (10.6 to 13.3)
2.0 to 2.5 (17.7 to 22.1)
5.4 to 6.0 (47.8 to 53.1)
9.9 to 11.0 (87.6 to 97.4)
5.4 to 6.0 (47.8 to 53.1)
9.9 to 11.0 (87.6 to 97.4)
9.9 to 11.0 (87.6 to 97.4)
Fuse Ampere
Rating (A)
25
25
60
80
100
125
175
25
25
25