Figure 2 EMC Standards Compliant Wiring of Single and Three Phase Units
Main and Control Circuit Wiring
Wiring the Main Circuit Input
Consider the following precautions for the main circuit input.
• Use fuses recommended in Main Circuit on
• When using residual current monitoring or detection devices (RCM/RCD), make sure the
devices are designed for use with AC drives (e.g. type B according to IEC/EN 60755).
• If using a ground fault circuit breaker, make sure that it can detect both DC and high
frequency current.
• Use a DC reactor or AC reactor on the input side of the drive:
–To suppress harmonic current.
–To improve the power factor on the power supply side.
–When using an advancing capacitor switch.
–With a large capacity power supply transistor (over 600 kVA).
Wiring the Main Circuit Output
Consider the following precautions for the output circuit wiring.
• Do not connect any other load than a 3 phase motor to the drives output.
• Never connect a power source to the drives output.
YASKAWA ELECTRIC TOEP C710606 15E - AC Drive V1000 - Quick Start Guide
Panel or mounting wall
Metal plate
Grounding Surface
(remove any paint)
R/L1 S/L2 T/L3
U/T1 V/T2 W/T3
Braid shielded motor
cable
Ground shield at
motor side
M
L2
L3
L3 L2 L1
EMC
Drive
Filter
Grounding
Surface
(remove any
paint)
Wiring distance as
short as possible
page 15
only.
3 Electrical Installation
L1 PE
Panel or mounting wall
Metal plate
Grounding Surface
(remove any paint)
E
R/L1 S/L2 T/L3
R/L1 S/L2 T/L3
U/T1 V/T2 W/T3
U/T1 V/T2 W/T3
Cable shield
grounding clamp
M
Drive
Grounding
Surface
(remove any
paint)
Braid shielded motor
cable
Ground shield at
motor side
EN 17