Terminal
U/T1, V/T2, W/T3
B1, B2
+1, +2
+1, –
(2 terminals)
Control Circuit Terminals
The figure below shows the control circuit terminal arrangement. The drive is equipped with
screwless terminals.
P1 P2 PC A1 A2 +V AC AM AC MP
S1 S2 S3 S4 S5 S6 SC HC H1 H2 RP
There are three DIP switches, S1 to S3, located on the terminal board.
SW1
Switches analog input A2 between voltage and current input.
SW2
Enables or disables the internal RS422/485 comm. port terminal resistance.
Used to select sourcing (PNP)/sinking (NPN, default) mode for the digital inputs (PNP requires
SW3
external 24 Vdc power supply).
YASKAWA ELECTRIC TOEP C710606 15E - AC Drive V1000 - Quick Start Guide
Type
Drive output
Connects to the motor.
Braking resistor
For connecting a braking resistor or the braking resistor unit option.
DC reactor
Linked at shipment. Remove the link to install a DC choke.
connection
DC power supply
For connecting a DC power supply.
input
For 200 V class: Ground with 100  or less
Ground Terminal
For 400 V class: Ground with 10  or less
S1
S2
S3
R+ R- S+ S- IG
MA MB MC
3 Electrical Installation
Function
Use a straght-edge screwdriver
with a blade width of max 2.5 mm
and a thickness of max 0.6 mm to
release the terminals