HOLIDAY SCHEDULING (FIG. 30) — Up to 18 different
holidays can be defined for special schedule consideration.
There are two different screens to be configured. First, in the
SERVICE / EQUIPMENT CONFIGURATION / HOLIDAYS
screen, select the first unused holiday entry (HOLDY01S, for
example). As shown in Fig. 30, enter a number for Start Month
(1 = January, 2 = February, ..., 12 = December), a number for
Start Day (1 - 31), and Duration in days (0 - 99). By default
there are no holidays set up. Second, in the occupancy Schedule
tables, specify and enable (by setting "X" under the "H" col-
umn) run time period(s) which will apply to all holidays. (Refer
to Fig. 20.) A run time period which is enabled for holidays may
be applied to one or more non-holiday days of the week as well.
This may be done for the local (table OCCPC01S), Ice Build
(OCCPC02S), and/or CCN (OCCPC03S) schedule(s). If the
chiller is on a CCN network, the active holiday definition will
be that configured in the device designated at the sole time
broadcaster (if one is so enabled). See the TIME BROADCAST
ENABLE section.
The broadcast function must be activated for the holidays
configured on the HOLIDEF screen to work properly. Access
the BRODEF screen from the EQUIPMENT CONFIGURA-
TION table and select ENABLE to activate function. Note that
when the chiller is connected to a CCN Network, only one
chiller or CCN device can be configured as the broadcast de-
vice. The controller that is configured as the broadcaster is the
device responsible for transmitting holiday, time, and daylight-
savings dates throughout the network.
To access the BRODEF screen, see the SERVICE menu
structure, Fig. 21.
To view or change the holiday periods for up to 18 different
holidays, perform the following operation:
1. At the Menu screen, press
vice menu.
2. If not logged on, follow the instructions for Attach to Net-
work Device or To Log Out. Once logged on,
press
until Equipment Configuration is high-
NEXT
lighted.
3. Once
Equipment
press
to access.
SELECT
4. Press
until HOLIDAYS is highlighted. This is
NEXT
the Holiday Definition table.
5. Press
to enter the Data Table Select screen.
SELECT
This screen lists 18 holiday tables.
6. Press
to highlight the holiday table that is to be
NEXT
viewed or changed. Each table is one holiday period,
starting on a specific date, and lasting up to 99 days.
7. Press
to access the holiday table. The Configu-
SELECT
ration Select table now shows the holiday start month and
day, and how many days the holiday period will last.
8. Press
NEXT
or
PREVIOUS
day, or duration.
to access the Ser-
SERVICE
Configuration
is
highlighted,
to highlight the month,
Fig. 30 — Example of Holiday Period Screen
9. Press
to modify the month, day, or duration.
SELECT
10. Press
INCREASE
ed value.
11. Press
to save the changes.
ENTER
12. Press
to return to the previous menu.
EXIT
DAYLIGHT SAVING TIME CONFIGURATION — The
BRODEF table also defines Daylight Saving Time changes.
This feature is by default enabled, and the settings should be
reviewed and adjusted if desired. The following line-item
entries are configurable for both Daylight Savings Time
"Start" and "Stop," and they are defined in Table 8.
To disable the Daylight Savings Time function simply enter
0 minutes for "Start Advance" and "Stop Back."
Table 8 — Daylight Saving Time Values
ITEM
MONTH
DAY OF WEEK
WEEK
TIME
ADVANCE/BACK
START-UP/SHUTDOWN/
RECYCLE SEQUENCE (FIG. 31)
Local Start-Up —
change when auto-restart after power failure is enabled and the
unit has been without power less than 20 minutes. See the
Auto Restart After Power Failure section. Local start-up (or a
manual start-up) is initiated by pressing the
softkey on the default ICVC screen. Local start-up can proceed
when the chiller schedule indicates that the CURRENT TIME
and CURRENT DATE have been established as a run time
and date, and after the internal 15-minute start-to-start and the
1-minute stop-to-start inhibit timers have expired. These timers
64
or
to change the select-
DECREASE
DEFINITION
1 = January, 2 = February, ...,
12 = December.
1 = Monday,..., 7 = Sunday
1 = first occurrence of selected
Day of Week in the selected
month, 2 = second occurrence
of the selected Day, etc. This is
not necessarily what one would
conclude from looking at a
standard calendar. For example,
April 7, 2011, is Day 4 Week 1,
but April 8, 2011, is Day 5
Week 2.
Time of day in 24-hour format
when the time advance or set
back will occur.
"Advance" occurs first in the
year, setting the time ahead by
the specified number of minutes
on the selected date. "Back"
sets the time back by the speci-
fied amount (later in the year).
The timing of a normal start-up will
LOCAL