Carrier AquaEdge 19XR series Installation Instructions Manual

Single-stage semi-hermetic centrifugal liquid chillers with pic ii controls and hfc-134a 50/60 hz

Advertisement

Quick Links

SAFETY CONSIDERATIONS

Centrifugal liquid chillers are designed to provide safe
and reliable service when operated within design specifi-
cations. When operating this equipment, use good judg-
ment and safety precautions to avoid damage to
equipment and property or injury to personnel.
Be sure you understand and follow the procedures and
safety precautions contained in the machine instruc-
tions, as well as those listed in this guide.
DANGER
Failure to follow these procedures will result in severe per-
sonal injury or death.
DO NOT VENT refrigerant relief devices within a build-
ing. Outlet from rupture disc or relief valve must be vented
outdoors in accordance with the latest edition of ANSI/
ASHRAE 15 (American National Standards Institute/
American Society of Heating, Refrigerating and Air-Con-
ditioning Engineers) (Safety Code for Mechanical Refrig-
eration). The accumulation of refrigerant in an enclosed
space can displace oxygen and cause asphyxiation.
PROVIDE adequate ventilation in accordance with ANSI/
ASHRAE 15, especially for enclosed and low overhead
spaces. Inhalation of high concentrations of vapor is harm-
ful and may cause heart irregularities, unconsciousness, or
death. Intentional misuse can be fatal. Vapor is heavier than
air and reduces the amount of oxygen available for breath-
ing. Product causes eye and skin irritation. Decomposition
products are hazardous.
DO NOT USE OXYGEN to purge lines or to pressurize a
machine for any purpose. Oxygen gas reacts violently with
oil, grease, and other common substances.
DO NOT USE air to leak test. Use only refrigerant or dry
nitrogen.
NEVER EXCEED specified test pressures. VERIFY the
allowable test pressure by checking the instruction litera-
ture and the design pressures on the equipment nameplate.
DO NOT VALVE OFF any safety device.
BE SURE that all pressure relief devices are properly
installed and functioning before operating any machine.
RISK OF INJURY OR DEATH by electrocution. High
voltage is present on motor leads even though the motor is
not running when a solid state or inside-delta mechanical
starter is used. Open the power supply disconnect before
touching motor leads or terminals.
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Catalog No. 04-53190043-01

Installation Instructions

Printed in U.S.A.
Form 19XR,XRV-CLT-12SI
Semi-Hermetic Centrifugal Liquid Chillers
with PIC II Controls and HFC-134a
WARNING
Failure to follow these procedures may result in personal
injury or death.
DO NOT USE TORCH to remove any component. System
contains oil and refrigerant under pressure.
To remove a component, wear protective gloves and gog-
gles and proceed as follows:
a. Shut off electrical power to unit.
b. Recover refrigerant to relieve all pressure from sys-
tem using both high-pressure and low pressure ports.
c. Traces of vapor should be displaced with nitrogen
and the work area should be well ventilated. Refrig-
erant in contact with an open flame produces toxic
gases.
d. Cut component connection tubing with tubing cutter
and remove component from unit. Use a pan to catch
any oil that may come out of the lines and as a gage
for how much oil to add to the system.
e. Carefully unsweat remaining tubing stubs when nec-
essary. Oil can ignite when exposed to torch flame.
DO NOT USE eyebolts or eyebolt holes to rig machine
sections or the entire assembly.
DO NOT work on high-voltage equipment unless you are a
qualified electrician.
DO NOT WORK ON electrical components, including
control panels, switches, starters, or oil heater until you are
sure ALL POWER IS OFF and no residual voltage can
leak from capacitors or solid-state components.
LOCK OPEN AND TAG electrical circuits during servic-
ing. IF WORK IS INTERRUPTED, confirm that all cir-
cuits are de-energized before resuming work.
AVOID SPILLING liquid refrigerant on skin or getting it
into the eyes. USE SAFETY GOGGLES. Wash any spills
from the skin with soap and water. If liquid refrigerant
enters the eyes, IMMEDIATELY FLUSH EYES with
water and consult a physician.
NEVER APPLY an open flame or live steam to a refriger-
ant cylinder. Dangerous over pressure can result. When it is
necessary to heat refrigerant, use only warm (110 F [43 C])
water.
DO NOT REUSE disposable (nonreturnable) cylinders or
attempt to refill them. It is DANGEROUS AND ILLE-
GAL. When cylinder is emptied, evacuate remaining gas
pressure, loosen the collar, and unscrew and discard the
valve stem. DO NOT INCINERATE.
CHECK THE REFRIGERANT TYPE before adding
refrigerant to the machine. The introduction of the wrong
refrigerant can cause machine damage or malfunction.
(Warnings continued on next page.)
Pg 1
AquaEdge
19XR,XRV
Single-Stage
50/60 Hz
12-16 Replaces: 19XR,XRV-CLT-11SI
®

Advertisement

Table of Contents
loading

Summary of Contents for Carrier AquaEdge 19XR series

  • Page 1: Safety Considerations

    ® AquaEdge 19XR,XRV Single-Stage Semi-Hermetic Centrifugal Liquid Chillers with PIC II Controls and HFC-134a 50/60 Hz Installation Instructions SAFETY CONSIDERATIONS WARNING Centrifugal liquid chillers are designed to provide safe and reliable service when operated within design specifi- Failure to follow these procedures may result in personal cations.
  • Page 2: Table Of Contents

    The 19XR, 19XRV machine is factory assem- General — CAN ENGAGE THE STARTER, TOWER FAN, OR bled, wired, and leak tested. Installation (not by Carrier) con- PUMPS. Open the disconnect ahead of the starter, tower sists primarily of establishing water and electrical services to fan, and pumps.
  • Page 3: Identify Machine

    2. Check all items against shipping list. Immediately notify Recommended Airflow Clearances — Be sure there is ade- the nearest Carrier representative if any item is missing. quate clearance for air circulation around the enclosure. 3. To prevent loss or damage, leave all parts in original A 6-in.
  • Page 4 51 3 19XR T* 64 – Description 19XR– — High Efficiency Semi-Hermetic Special Order Indicator Centrifugal Liquid Chiller – — Standard S — Special Order 19XRV — High Efficiency Semi-Hermetic Centrifugal Liquid Chiller with Unit-Mounted VFD Motor Voltage Code Code Volts-Phase-Hertz Cooler Size†...
  • Page 5 FRONT VIEW LEGEND 1 — Guide Vane Actuator 2 — Suction Elbow 3 — International Chiller Visual Control (ICVC) 4 — Chiller Identification Nameplate 5 — Cooler Auto Reset Relief Valves 6 — Cooler Pressure Transducer 7 — Condenser In/Out Temperature Thermistors 8 —...
  • Page 6: Frame

    CLEARANCE FOR FRAME 2-4 COMPRESSOR 3'-0" (915 mm) MOTOR SERVICE TUBE REMOVAL RECOMMENDED OVERHEAD SERVICE CLEARANCE CLEARANCE SPACE FOR FRAME 5 COMPRESSOR 5'-0" (1524 mm) 4'-0"- (1219 mm) EITHER END RECOMMENDED OVERHEAD SERVICE CLEARANCE 10'-0" (3048 mm) (SIZES 10-12, 20-22) 12'-3 1/2"...
  • Page 7: Frame

    *Assumes both cooler and condenser nozzles on same end of 3. Dimensions are approximate. Certified drawings available upon chiller. request. †Compressor frame size 2. 4. Marine waterboxes may add 6 in. to the width of the machine. **Compressor frame size 3. See certified drawings for details.
  • Page 8: Frame

    MAXIMUM MACHINE CHAIN LENGTH WEIGHT FREE- VESSEL DIM. “A” DIM. “B” DIM. “C” COMP HEAT STANDING LENGTH 700L 575-V FRAME EXCH UNIT- “D” “E” “F” SIZE SIZE MOUNTED STARTER 10-12 18,590 8432 — — 3048 1397 12-7 3835 13-0 3962 13-0 3962 15-17...
  • Page 9: Frame

    MAXIMUM CHAIN LENGTH VESSEL COMP HEAT MACHINE DIM. “A” DIM. “B” DIM. “C” LENGTH FRAME EXCH “D” “E” “F” WEIGHT SIZE SIZE ft-in. ft-in. ft-in. ft-in. ft-in. ft-in. 70-74 46,119 20919 4267 6- 2 1880 1067 1397 11- 6 3505 12-5 3785 12-9...
  • Page 10: Frame

    (compressor weight column), stator, rotor, and not included. Applicable to standard compressors only. For high lift end bell cover weights. compressors, contact Carrier Chiller Marketing for weights. †See Model Number Nomenclature in Fig. 2. ††Stator weight includes the stator and shell.
  • Page 11: Frame

    (compressor weight column), stator, rotor, and not included. Applicable to standard compressors only. For high lift end bell cover weights. compressors, contact Carrier Chiller Marketing for weights. †See Model Number Nomenclature in Fig. 2. ††Stator weight includes the stator and shell.
  • Page 12: Frame

    (compressor weight column), stator, rotor, and not included. Applicable to standard compressors only. For high lift end bell cover weights. compressors, contact Carrier Chiller Marketing for weights. †See Model Number Nomenclature in Fig. 2. ††Stator weight includes the stator and shell.
  • Page 13: Frame

    Applicable to standard compressors only. For high lift end bell cover weights. compressors, contact Carrier Chiller Marketing for weights. For com- †See Model Number Nomenclature in Fig. 2. pressor frame size 4, two compressor weights are shown. The sec- ond value, 4211 lb (1910 kg), represents the weight when the compressor is equipped with a split ring diffuser (SRD).
  • Page 14 Applicable to standard compressors only. For high lift end bell cover weights. compressors, contact Carrier Chiller Marketing for weights. For com- †See Model Number Nomenclature in Fig. 2. pressor frame size 4, two compressor weights are shown. The sec- ond value, 4211 lb (1910 kg), represents the weight when the compressor is equipped with a split ring diffuser (SRD).
  • Page 15 (compressor weight column), stator, rotor, and not included. Applicable to standard compressors only. For high lift end bell cover weights. compressors, contact Carrier Chiller Marketing for weights. †See Model Number Nomenclature in Fig. 2. ††Stator weight includes the stator and shell.
  • Page 16 (compressor weight column), stator, rotor, and not included. Applicable to standard compressors only. For high lift end bell cover weights. compressors, contact Carrier Chiller Marketing for weights. †See Model Number Nomenclature in Fig. 2. ††Stator weight includes the stator and shell.
  • Page 17 Table 6A — 19XR Heat Exchanger Data — Drive End Entering Cooler Water ENGLISH METRIC (SI) DRY RIGGING WEIGHT DRY RIGGING WEIGHT MACHINE CHARGE MACHINE CHARGE (LB)* (KG)* CODE† REFRIGERANT WATER WEIGHT REFRIGERANT WATER WEIGHT COOLER CONDENSER COOLER CONDENSER WEIGHT (LB) (LB) WEIGHT (KG) (KG)
  • Page 18 Table 6A — 19XR Heat Exchanger Data — Drive End Entering Cooler Water (cont) ENGLISH METRIC (SI) DRY RIGGING WEIGHT DRY RIGGING WEIGHT MACHINE CHARGE MACHINE CHARGE (LB)* (KG)* CODE REFRIGERANT WATER WEIGHT REFRIGERANT WATER WEIGHT COOLER CONDENSER COOLER CONDENSER WEIGHT (LB) (LB) WEIGHT (KG)
  • Page 19 Table 6B — 19XR Heat Exchanger Data — Compressor End Entering Cooler Water ENGLISH METRIC (SI) DRY RIGGING WEIGHT DRY RIGGING WEIGHT MACHINE CHARGE MACHINE CHARGE (LB)* (KG)* CODE† REFRIGERANT WATER WEIGHT REFRIGERANT WATER WEIGHT COOLER CONDENSER COOLER CONDENSER WEIGHT (LB) (LB) WEIGHT (KG) (KG)
  • Page 20 Table 6B — 19XR Heat Exchanger Data — Compressor End Entering Cooler Water (cont) ENGLISH METRIC (SI) DRY RIGGING WEIGHT DRY RIGGING WEIGHT MACHINE CHARGE MACHINE CHARGE (LB)* (KG)* CODE REFRIGERANT WATER WEIGHT REFRIGERANT WATER WEIGHT COOLER CONDENSER COOLER CONDENSER WEIGHT (LB) (LB) WEIGHT (KG)
  • Page 21 Table 7 — 19XR Additional Data for Marine Waterboxes* ENGLISH HEAT EXCHANGER RIGGING WEIGHT (LB) WATER VOLUME (GAL) RIGGING WEIGHT (KG) WATER VOLUME (L) FRAME, PASS PSIG COOLER CONDENSER COOLER CONDENSER COOLER CONDENSER COOLER CONDENSER FRAME 2, 1 AND 3 PASS —...
  • Page 22 Table 8A — 19XR Waterbox Cover Weights — English (lb COOLER FRAME 1 FRAME 2 FRAME 3 WATERBOX DESCRIPTION STANDARD STANDARD STANDARD FLANGED FLANGED FLANGED NOZZLES NOZZLES NOZZLES NIH, 1 Pass Cover, 150 psig NIH, 2 Pass Cover, 150 psig NIH, 3 Pass Cover, 150 psig MWB End Cover, 150 psig —...
  • Page 23 Table 8A — 19XR Waterbox Cover Weights — English (lb) (cont) COOLER FRAME 4 FRAME 5 FRAME 6 WATERBOX DESCRIPTION STANDARD STANDARD STANDARD FLANGED FLANGED FLANGED NOZZLES NOZZLES NOZZLES NIH, 1 Pass Cover, 150 psig NIH, 2 Pass Cover, 150 psig NIH, 3 Pass Cover, 150 psig MWB End Cover, 150 psig MWB Return Cover, 150 psig...
  • Page 24 Table 8A — 19XR Waterbox Cover Weights — English (lb) (cont) COOLER FRAME 7 FRAME 8 WATERBOX DESCRIPTION STANDARD STANDARD FLANGED FLANGED NOZZLES NOZZLES NIH, 1 Pass Cover, 150 psig NIH, 2 Pass Cover, 150 psig NIH, 3 Pass Cover, 150 psig 1250 1291 1629...
  • Page 25 Table 8B — 19XR Waterbox Cover Weights — SI (kg) COOLER FRAME 1 FRAME 2 FRAME 3 WATERBOX DESCRIPTION STANDARD STANDARD STANDARD FLANGED FLANGED FLANGED NOZZLES NOZZLES NOZZLES NIH, 1 Pass Cover, 1034 kPa NIH, 2 Pass Cover, 1034 kPa NIH, 3 Pass Cover, 1034 kPa MWB End Cover, 1034 kPa —...
  • Page 26 Table 8B — 19XR Waterbox Cover Weights — SI (kg) (cont) COOLER FRAME 4 FRAME 5 FRAME 6 WATERBOX DESCRIPTION STANDARD STANDARD STANDARD FLANGED FLANGED FLANGED NOZZLES NOZZLES NOZZLES NIH, 1 Pass Cover, 1034 kPa NIH, 2 Pass Cover, 1034 kPa NIH, 3 Pass Cover, 1034 kPa MWB End Cover, 1034 kPa NIH/MWB Return Cover, 1034 kPa...
  • Page 27: Rig Machine Components

    MWB — Marine Waterbox RIG MACHINE COMPONENTS — Refer to instructions NOTE: Wiring must also be disconnected. Label each wire below, Fig. 7-10, and Carrier Certified Prints for machine com- before removal (see Carrier Certified Prints). In order to dis- ponent disassembly.
  • Page 28 b. water-side transducer cables at the transducer g. compressor oil discharge pressure cable (Fig. 10, (Fig. 9, Item 4) Item 5) c. condenser transducer cable at the transducer h. guide vane actuator cable (Fig. 8, Item 1) (Fig. 9, Item 7) i.
  • Page 29 a19-1391ef 1 — Guide Vane Actuator Cable 6 — Compressor Discharge Elbow Joints 2 — Power Panel 7 — Condenser Pressure Cable 3 — Communication Cable 8 — Cooler Pressure Connection 4 — Water Sensor Cables 9 — Water Sensor Cables 5 —...
  • Page 30 a19-1390tf 1 — Motor Temperature Sensor Cable 5 — Compressor Oil Discharge Pressure Cable 2 — Bearing Temperature Sensor Cable 6 — Discharge Temperature Sensor Cable Connection (Inside Box) 7 — Guide Vane Actuator Cable 3 — Compressor Oil Sump Pressure Cable 8 —...
  • Page 31: Step 3 - Install Machine Supports

    For adequate and long lasting machine support, proper Step 3 — Install Machine Supports grout selection and placement is essential. Carrier recommends INSTALL STANDARD ISOLATION — Figures 11 and 12 that only pre-mixed, epoxy type, non-shrinking grout be used show the position of support plates and shear flex pads, which for machine installation.
  • Page 32: Install Spring Isolation

    INSTALL SPRING ISOLATION — Spring isolation may NOTE: It is recommended that any installation other than the be purchased as an accessory from Carrier for field installation. ground floor should have spring isolation for the chiller and It may also be field supplied and installed. Spring isolators may piping vibration isolation.
  • Page 33 NOTES: 1. Dimensions in ( ) are in millimeters. 2. Accessory (Carrier supplied, field installed) soleplate package includes 4 soleplates, 16 jacking screws and leveling pads. 3. Jacking screws to be removed after grout has set. 4. Thickness of grout will vary, depending on the amount necessary to level chiller. Use only pre-mixed non-shrinking grout, Ceilcote 748 or Chemrex Embeco 636 Plus Grout, 1½...
  • Page 34: Step 4 - Connect Piping

    for adjusting the piping in each plane and for periodic and Step 4 — Connect Piping major servicing of the equipment. INSTALL WATER PIPING TO HEAT EXCHANG- 5. Water flow direction must be as specified in Fig. 16-19. ERS — Refer to Table 9 for nozzle sizes. Install piping using job data, piping drawings, and procedures outlined below.
  • Page 35 NOZZLE-IN HEAD WATERBOXES a19-1370tf FRAMES 1, 2, AND 3 FRAMES 4, 5, AND 6 a19-1243tf NOZZLE ARRANGEMENT CODES FOR ALL 19XR NOZZLE-IN-HEAD WATERBOXES COOLER WATERBOXES CONDENSER WATERBOXES PASS PASS ARRANGEMENT ARRANGEMENT CODE* CODE* *Refer to certified drawings. Fig. 16 — Piping Flow Data (NIH, Frames 1 Through 6)
  • Page 36 NOZZLE-IN HEAD WATERBOXES COND COND COOLER COOLER a19-1548ef COMPRESSOR END DRIVE END FRAMES 7 AND 8 NOZZLE ARRANGEMENT CODES FOR ALL 19XR NOZZLE-IN-HEAD WATERBOXES COOLER WATERBOXES CONDENSER WATERBOXES PASS PASS ARRANGEMENT CODE* ARRANGEMENT CODE* *Refer to certified drawings. Fig. 17 — Piping Flow Data (NIH, Frames 7 and 8) MARINE WATERBOXES a19-1245tf FRAMES 2 AND 3*...
  • Page 37 MARINE WATERBOXES a19-1245tf FRAMES 4, 5, AND 6 NOZZLE ARRANGEMENT CODES COOLER WATERBOXES CONDENSER WATERBOXES PASS ARRANGEMENT ARRANGEMENT CODE CODE — — — — — — — — — — — — a19-1247tf FRAMES 7 AND 8 NOZZLE ARRANGEMENT CODES COOLER WATERBOXES CONDENSER WATERBOXES PASS...
  • Page 38 Table 9 — 19XR Waterbox Nozzle Sizes NOMINAL PIPE SIZE (IN.) ACTUAL PIPE ID (IN.) FRAME PRESSURE PASS SIZE PSIG (KPA) COOLER CONDENSER COOLER CONDENSER 7.981 7.981 150/300 6.065 6.065 (1034/2068) 6.065 6.065 10.020 10.020 150/300 7.981 7.981 (1034/2068) 6.065 6.065 10.020 10.020...
  • Page 39 3/8" MALE FLARE RELIEF VALVE CONN. LEVEL GAGE 0' - 9 " 1/2" DIA. K.O. [229mm] ELECTRICAL CONN. TYPICAL (PUMPOUT POWER) 0' - 5 1/2" [140mm] (2) 1" NPT RELIEF VALVE OUTLET (SEE FIELD PRESSURE GAGE INSTALLATION NOTES) 1' - 7 " [483mm] 0' - 5 7/8 "...
  • Page 40 RATED DRY WEIGHT AND REFRIGERANT CAPACITY) ENGLISH (LB) SI (KG) MAXIMUM REFRIGERANT CAPACITY MAXIMUM REFRIGERANT CAPACITY TANK TANK OD TANK TANK OD (LB) (KG) WEIGHT* WEIGHT* SIZE (IN.) SIZE (MM) (LB) (KG) ANSI/ASHRAE 15 UL 1963 ANSI/ASHRAE 15 UL 1963 0428 24.00 2334...
  • Page 41: Install Vent Piping To Relief Valves

    11 for size and location of relief devices. Vent relief devices to the outdoors in accordance with ANSI/ASHRAE 15 (latest FRAME edition) Safety Code for Mechanical Refrigeration and all ASSEMBLY CONTROL other applicable codes. PANEL DANGER Refrigerant discharged into confined spaces can displace oxygen and cause asphyxiation.
  • Page 42 WITH OPTIONAL ISOLATION OF DISCHARGE AND COOLER (Fig. A, B) a19-1497ef a19-1496ef FIG. A FIG. B FRAME 1-6 FRAMES 7, 8 WITHOUT ISOLATION OPTION OF DISCHARGE AND COOLER (Fig. C, D) a19-1498ef a19-1499ef FIG. C FIG. D FRAME 1-6 FRAME 7, 8 CONDENSER RELIEF VALVE ARRANGEMENT —...
  • Page 43: Install Circuit Breaker Handle

    Additional spare sen- Fig. 25 — Circuit Breaker Handle Extension sors and Carrier Comfort Network ® modules may be specified as well. These are wired to the machine control panel as indi- cated in Fig.
  • Page 44 a19-1502tf...
  • Page 45 a19-1943...
  • Page 46: Connect Control Outputs

    (Low Fan, High Fan) • 4 to 20 mA Resets • Optional Remote Sensors 12 — Strainers 3. IMPORTANT: Carrier suggests that a structural engineer be Piping consulted if transmission of vibrations from mechanical equip- ment is of concern. Control Wiring 4.
  • Page 47 LEGEND FOR FIG. 30 19XR with Unit-Mounted Starter REFERENCE EXPLANATION NUMBER 3 Phase Under/Over Voltage Phase Loss/Imbalance/Reversal Motor Overload Protection Frequency Shift kW Transducer/kW Hours/Demand kW Single Cycle Dropout Motor/Starter Overcurrent Control Power Transformer (3KVA) (Integral) Controls and Oil Heater Circuit Breaker (integral) Oil Pump Circuit Breaker (Integral) 4-20ma Head Pressure Reference Output 3 Phase Analog Volts/Amps Meter Package...
  • Page 48 a19-2006 NOTE: See Legend on page 47. Fig. 30 — 19XR Typical Field Wiring with Unit-Mounted Starter...
  • Page 49 a19-1504ef Fig. 30 — 19XR Typical Field Wiring with Unit-Mounted Starter (cont)
  • Page 50 CAUTION CONDUCTORS 186-207A 3 AWG — 350 MCM Control wiring for Carrier to start pumps and tower fan motors and establish flows must be provided to assure machine protec- 208-296A 2/0 AWG — 250 MCM tion. If primary pump, tower fan, and flow control is by other 297-444A 250 —...
  • Page 51 LEGEND FOR FIG. 31 19XR with Unit-Mounted VFD with ISM REFERENCE EXPLANATION NUMBER 3 Phase Under/Over Voltage (Line Side) Phase Loss/Imbalance/Reversal (Line Side) Frequency Shift (Line Side) kW Transducer/kW Hours/Demand kW Over Current Control Power Transformer (3KVA) Controls and Oil Heater Fused Disconnect (FU2) Oil Pump Circuit Fused Disconnect (FU1) Phase to Ground Fault Protection 3 Phase Analog Volts/Amps Meter Package...
  • Page 52 a19-2078 NOTE: See Legend on page 51. Fig. 31 — 19XR Typical Wiring with Unit-Mounted Variable Frequency Drive with ISM (Integrated Start Module)
  • Page 53 a19-1714 Fig. 31 — 19XR Typical Wiring with Unit-Mounted Variable Frequency Drive with ISM (Integrated Start Module) (cont)
  • Page 54 CAUTION 1.3 Equipment installation and all starting and control devices, Control wiring for Carrier to start pumps and tower fan motors must comply with details in equipment submittal drawings and establish flows must be provided to assure machine protec- and literature.
  • Page 55 3. Oil pump disconnect may be located within the enclosure of Item 2 — Free-standing Compressor Motor Starter. 11 — Condensing Water Pump Starter 4. IMPORTANT: Carrier suggests that a structural engineer be 12 — Cooling Tower Fan Starter consulted if transmission of vibrations from mechanical equip- (Low Fan, High Fan) ment is of concern.
  • Page 56 a19-2007 NOTE: See Legend on page 58. Fig. 33 — 19XR Typical Field Wiring with Free-Standing Starter (Low Voltage)
  • Page 57 a19-1506ef (SEE NOTE 3.8) Fig. 33 — 19XR Typical Field Wiring with Free-Standing Starter (Low Voltage) (cont)
  • Page 58 LEGEND FOR FIG. 33 19XR with Free-Standing Starter (Low Voltage) REFERENCE EXPLANATION NUMBER 3 Phase Under/Over Voltage Phase Loss/Imbalance/Reversal Motor Overload Protection Frequency Shift kW Transducer/kW Hours/Demand kW Single Cycle Dropout Motor/Starter Overcurrent Control Power Transformer (3KVA) (Integral) Controls and Oil Heater Circuit Breaker (integral) Oil Pump Circuit Breaker 3 Phase Analog Volts/Amps Meter Package Power Factor Correction Package...
  • Page 59 4.0 Low voltage (600 v or less) compressor motors have (6) wiring connections. in. terminal studs (lead connectors not supplied by Carrier). Either 3 or 6 conductors must be run between 1.2 The routing of field-installed conduit and conductors and compressor motor and starter, depending on the size of the the location of field-installed devices must not interfere with conductors or the type of motor starter employed.
  • Page 60 a19-2008 NOTE: See Legend on page 62. Fig. 34 — 19XR Typical Field Wiring with Free-Standing Starter (Medium Voltage)
  • Page 61 a19-1508ef (SEE NOTE 3.8) Fig. 34 — 19XR Typical Field Wiring with Free-Standing Starter (Medium Voltage) (cont)
  • Page 62 LEGEND FOR FIG. 34 19XR with Free-Standing Starter (Medium Voltage) REFERENCE EXPLANATION NUMBER 3 Phase Under/Over Voltage Phase Loss/Imbalance/Reversal Motor Overload Protection Frequency Shift kW Transducer/kW Hours/Demand kW Single Cycle Dropout Motor/Starter Overcurrent Control Power Transformer (3KVA) (Integral) Controls and Oil Heater Circuit Breaker (integral) Oil Pump Circuit Breaker Oil Pump Circuit Breaker with Transformer 3 Phase Analog Volts/Amps Meter Package...
  • Page 63 National Electrical Code (NFPA-70) and applicable CAUTION codes. Means for grounding compressor motor is a #4 Control wiring for Carrier to start pumps and tower fan motors AWG to 500 MCM pressure connector, supplied and and establish flows must be provided to assure machine protec- located in the lower left side corner of the compressor tion.
  • Page 64 DRIVE INPUT CONTACTOR DRIVE INPUT OVERLOAD LV AND 1 115 V POWER SUPPLY IS REQUIRED AND MUST BE FIELD SUPPLIED WITH BRANCH CIRCUIT PROTECTION (8 kVA MINIMUM REQUIRED) CARRIER ISM MODULE CONTROL POWER DISCONNECT TRANSFORMER ISOLATED GATE SWITCH 1 DRIVE...
  • Page 65 a19-2065...
  • Page 66 a19-2059...
  • Page 67 — Surge Suppressor — Variable Frequency Drive Surge Suppressor — Warning Relay POWER ELECTRONIC DEVICES Carrier ISM to be programmed by Carrier before Symmetrical Gate-Commutated Thyristor and start-up. Relay contacts shown without signal Gate Driver Board power applied. Located in drive low voltage control section. Wire MISCELLANEOUS with #12 AWG.
  • Page 68 AWG to 500 MCM pressure connector, supplied and located in the lower left side corner of the compressor Control wiring for Carrier to start pumps and tower fan motors motor terminal box. and establish flows must be provided to assure machine protec- tion.
  • Page 69 LEGEND FOR FIG. 36 19XR with Free-Standing Low Voltage VFD REFERENCE EXPLANATION NUMBER 3 Phase Under/Over Voltage Phase Loss/Imbalance/Reversal Motor Overload Protection Frequency Shift kW Transducer/kW Hours/Demand kW Single Cycle Dropout Motor/Starter Overcurrent Control Power Transformer (3KVA) (Integral) Controls and Oil Heater Circuit Breaker (integral) Oil Pump Circuit Breaker (Integral) Phase to Ground Fault Protection 3 Phase Analog Volts/Amps Meter Package...
  • Page 70 a19-1949 NOTE: See Legend on page 69. Fig. 36 — 19XR Typical Field Wiring with Free-Standing Low Voltage VFD...
  • Page 71 a19-1508ef (SEE NOTE 3.8 Fig. 36 — 19XR Typical Field Wiring with Free-Standing Low Voltage VFD (cont)
  • Page 72 CAUTION 4.4 Compressor motor frame to be grounded in accordance Control wiring for Carrier to start pumps and tower fan motors with the National Electrical Code (NFPA-70) and applicable and establish flows must be provided to assure machine protec- codes.
  • Page 73: Carrier Comfort Network Interface

    Voltage to terminals LL1 and LL2 (of each circuit) comes panel. All control wiring must use shielded cable. Also, con- from a control transformer in a starter built to Carrier speci- nect the communications cable. Refer to the job wiring dia- fications.
  • Page 74: Optional Upc Open Controller Wiring

    At each system element, the shields of its communication To wire the UPC Open controller to the BAS network: bus cables must be tied together. If the communication bus is 1. Pull the screw terminal connector from the controller's entirely within one building, the resulting continuous shield BAS Port.
  • Page 75 BT485 TERMINATOR BACNET CONNECTION POWER LED (BAS PORT) Tx1 LED Rx1 LED Tx2 LED Rx2 LED BACNET BAUD RATE DIP SWITCHES EIA-485 JUMPERS ADDRESS ROTARY SWITCHES RUN LED ERROR LED Fig. 40 — UPC Open Controller Fig. 41 — Network Wiring...
  • Page 76 Fig. 42 — BT485 Terminator Installation...
  • Page 77 Table 12 — MS/TP Wiring Recommendations SPECIFICATION RECOMMENDATION CABLE Single twisted pair, low capacitance, CL2P, 22 AWG (7x30), TC foam FEP, plenum rated cable CONDUCTOR 22 or 24 AWG stranded copper (tin plated) INSULATION Foamed FEP 0.015 in. (0.381 mm) wall 0.060 in. (1.524 mm) O.D. COLOR CODE Black/White TWIST LAY...
  • Page 78: Step 6 - Install Field Insulation

    • cooler shell a19-1563ef a19-1564ef Fig. 43 — 19XR Insulation Area © Carrier Corporation 2016 Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations. Catalog No. 04-53190043-01 Printed in U.S.A.
  • Page 79: Checklist

    9. The motor starter has not been supplied by Carrier and it has been checked for proper operation. Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
  • Page 80 Concerns about the installation/request for additional assistance: I am aware that the start-up time for a Carrier chiller can take between 2 and 6 days depending on the model of the machine and the options and accessories used with it.

This manual is also suitable for:

Aquaedge 19xrv series

Table of Contents