DESCRIPTION
Base Demand Limit
LCW Setpoint
ECW Setpoint
Ice Build Setpoint
Tower Fan High Setpoint
ICVC Software Version Number:
ICVC Controller Identification: BUS:
19XR, XRV PIC II SETPOINT TABLE CONFIGURATION SHEET
RANGE
40 to 100
10 to 120
-9.4 to 48.9
15 to 120
-12.2 to 48.9
15 to 60
-9.4 to 15.6
55 to 105
13 to 41
UNITS
DEFAULT
%
100
DEG F
50.0
DEG C
10.0
DEG F
60.0
DEG C
15.6
DEG F
40.0
DEG C
4.4
DEG F
75
DEG C
24
ADDRESS:
CL-3
VALUE