Carrier AquaEdge 19XR series Start-Up, Operation And Maintenance Instructions Manual page 207

Single-stage or two-stage semi-hermetic centrifugal liquid chillers with pic ii controls and hfc-134a 50/60 hz
Table of Contents

Advertisement

DESCRIPTION
Capacity Control
Proportional Inc Band
Proportional DEC Band
Proportional ECW Gain
Guide Vane Travel Limit
VFD Speed Control
VFD Option
VFD Gain
VFD Increase Step
VFD Minimum Speed
VFD Maximum Speed
VFD Start Speed
VFD Surge Line Gain
VFD Current Limit
19XR, XRV PIC II SETUP2 TABLE CONFIGURATION SHEET
STATUS
2 to 10
2 to 10
1 to 3
30 to 100
0/1
0.1 to 1.5
1 to 5
65 to 100
90 to 100
65 to 100
2.0 to 3.5
0 to 99999
UNITS
%
DSABLE/ENABLE
%
%
%
%
amps
CL-9
DEFAULT
VALUE
6.5
6.0
2.0
80
DSABLE
0.75
2
70
100
100
2.0
250