Vfd Field Setup And Verification - Carrier AquaEdge 19XR series Start-Up, Operation And Maintenance Instructions Manual

Single-stage or two-stage semi-hermetic centrifugal liquid chillers with pic ii controls and hfc-134a 50/60 hz
Table of Contents

Advertisement

automatically after power-up. Current and Ramp Time config-
urations are entered in the CFN menu. CT Ratio configuration
is entered in the FUN menu. See Table 13 for menu structure
and Table 14 for settings.
1. Press the
softkey until the desired menu is select-
MENU
ed on the display.
2. Press the
softkey to access the displayed menu
ENTER
items (Table 14).
3. Use the
or
arrow keys to scroll between menu items
until the desired item is reached on the display.
4. Press the
softkey to access the value to be
ENTER
changed.
5. Use the
or
arrow keys to adjust the new displayed
value. The
key increases the value while the
decreases the value. Holding the arrow key will progres-
sively increase the rate of change. The value will stop
changing when either the factory set minimum or maxi-
mum value is reached. To make fine adjustments press
and release the arrow key.
6. When the correct value has been selected, press
the
key to store the new configuration. At this
ENTER
point, there are two options. The
the display to the main display. The
will move the display to the next menu item. When fin-
ished press the
MENU
To view other settings and troubleshooting guide consult the
Benshaw RediStart MICRO instructional manual included in
the starter.
PARAMETER
ISM_CONF — Select 0 for full voltage, 1 for
Starter Type
reduced voltage, or 2 for solid state or 3 for vari-
able frequency drive.
Motor Rated Line
ISM_CONF — Motor rated voltage from chiller
Voltage
information nameplate.
ISM_CONF — Enter ratio (reduced to a ratio to
Volt Transformer
1) of power transformer wired to terminal J3 of
Ratio
ISM. If no transformer is used enter 1.
Motor Rated
ISM_CONF — Per chiller nameplate data. RL
Load Amps
AMPS on compressor nameplate.
Motor Locked
ISM_CONF — Per chiller identification name-
Rotor Trip
plate.
ISM_CONF — Enter value from nameplate in
Starter LRA
starter cabinet MAXIMUM FUSE. This value
Rating
shall always be "9999" for Benshaw RediStart
MX3 wye-delta and solid-state starters.
ISM_CONF — Enter ratio (reduced to a ratio to
1) of current transformers wired to terminal J4 of
Motor Current
ISM. This value shall always be "100" for Ben-
CT Ratio
shaw RediStart MX3 wye-delta and solid-state
starters.
ISM_CONF — Current imbalance trip threshold.
Current% Imbalance
Enter up to 100% for starter type 3 (VFD).
Ground Fault
ISM_CONF — Enter 0 if no ground fault CTs are
Current
wired to terminal J5 of ISM. Enter 1 if ground
Transformers
fault CTs are used.
Ground Fault
ISM_CONF — Enter ratio (reduced to a ratio to
CT Ratio
1) of ground fault CT.
ISM_CONF — ENABLE if motor protection
Single Cycle
required from drop in line voltage within one
Dropout
cycle.
ISM_CONF — Enter YES for 60 Hz or NO for
Line Frequency
50 Hz.
ISM_CONF — ENABLE if motor
Line Frequency
protection required for drop in line
Faulting
frequency.
Surge Limit/Hot Gas
OPTIONS — Enter 1 or 2 if HGBP is installed.
Bypass Option
Enter 0 otherwise.
*With variable flow systems this point may be configured to the lower end of
the range.
NOTE: Other parameters: Screens are normally left at the default settings;
they may be changed by the operator as required. The time and persistence
settings on the ISM_CONF table can be adjusted to increase or decrease the
sensitivity to a fault condition. Increasing time or persistence decreases sensi-
tivity. Decreasing time or persistence increases sensitivity to the fault
condition.
key will return
MENU
or
arrow keys
key to return to the main display.
Table 12 — Job Site Parameters
TABLE

VFD Field Setup and Verification

IMPORTANT: The VFD controller has been factory config-
ured for use and communications to the International Chiller
Visual Controller (ICVC). Some parameters are specific to
the chiller configuration and will need to be verified prior to
operation. Speed control and starting the drive have been
disabled at the VFD keypad. All command functions must
be initiated from the ICVC.
key
Fig. 35 — Benshaw RediStart
a19-1958
PARAMETER
Minimum Load
Points (Tsmin, IGVmin)
Full (Maximum) Load
Points (Tsmax, IGVmax)
Surge Line Shape Factor
(shapefac)
Chilled Medium
Evaporator
Refrigerant
Trippoint
Evaporator Flow
Delta P Cutout
Condenser Flow
Delta P Cutout
High Condenser Water
Delta P
VFD Option
VFD Current List
Diffuser Option
(Compressors with Split
Ring Diffusers)
Diffuser Full Span mA
(Compressors with Split
Ring Diffusers)
Motor Rated
Kilowatts
75
MICRO Default Display
TABLE
OPTIONS — Per Chiller Requisition (Tsmin,
IGVmin) if available or per job data — See mod-
ify load points section. Refer to table located in
the control panel.
OPTIONS — Per Chiller Requisition (Tsmax,
IGVmax) if available or per job data — See mod-
ify load points section. Refer to table located in
the control panel.
OPTIONS — Per Chiller Requisition (shapefac).
Refer to table located in the control panel.
SETUP1 — Enter water or brine.
SETUP1 — Usually 3° F (1.7° C) below design
refrigerant temperature.
SETUP1 — Per Chiller Requisition if available or
enter 50% of design pressure drop to 0.5 psi
(3.4 kPa).*
SETUP1 — Per Chiller Requisition if available or
enter 50% of design pressure drop to 0.5 psi
(3.4 kPa).*
SETUP1 — Enter the maximum allowable value
for condenser water pressure drop.
SETUP2 — ENABLE if a VFD is supplied for the
chiller.
SETUP2 — Enter the value fo the full load output
amps of the VFD.
VDO_SRD — ENABLE for 4 and 5 size com-
pressor with split ring diffusers. See model num-
ber nomenclature.
SETUP2 VDO_SRD — Enter diffuser actuator
full span mA rating for 4 and 5 size compressor.
Value is located on label on side of diffuser actu-
ator motor.
RAMP_DEM — Enter value from chiller requisi-
tion form (product data submittal) if DEMAND
LIMIT SOURCE is set to kW.