Carrier AquaEdge 19XR series Start-Up, Operation And Maintenance Instructions Manual page 113

Single-stage or two-stage semi-hermetic centrifugal liquid chillers with pic ii controls and hfc-134a 50/60 hz
Table of Contents

Advertisement

Custom Alarm/Alert Messages with Troubleshooting Guides (cont)
K. ISM ALARMS (cont)
ICVC
FAULT
PRIMARY MESSAGE
STATE
217
PROTECTIVE LIMIT
218
PROTECTIVE LIMIT
219
PROTECTIVE LIMIT
220
PROTECTIVE LIMIT
221
PROTECTIVE LIMIT
222
PROTECTIVE LIMIT
223
PROTECTIVE LIMIT
224
PROTECTIVE LIMIT
*[LIMIT] is shown on the ICVC as the temperature, pressure, voltage, etc., set point predefined or selected by the operator as an override, alert, or
alarm condition. [VALUE] is the actual pressure, temperature, voltage, etc., at which the control tripped. "Exceeded Limit" in Alarm or Alert mes-
sages may mean the value is above or below a threshold.
Table 16 — ICVC Primary and Secondary Messages and
SECONDARY MESSAGE
MOTOR OVERLOAD TRIP
MOTOR LOCKED ROTOR TRIP
STARTER LOCK ROTOR TRIP
GROUND FAULT
PHASE REVERSAL TRIP
LINE FREQUENCY TRIP
STARTER MODULE FAILURE
1CR START CIRCUIT FAULT
PRIMARY CAUSE
217->Motor Overload Trip; Check ISM
Configurations
218->Motor Locked Rotor Amps
Exceeded;Check Motor and ISM Config
219->Starter Locked Rotor Amps Rating
Exceeded
220->Ground Fault Trip; Check Motor
and Current Transformers
221-> Phase Reversal Trip; Check
Power Supply
222->Line Frequency - [VALUE]
exceeded limit of [LIMIT]*; Check Power
Supply.
223->Starter Module Hardware Failure
224->Check 115v Wiring to 1CR (ISM)
and to 1M Coil
113
ADDITIONAL
CAUSE/REMEDY
Any phase current > 108% RLA for excessive time
period. Alarm can result from significant load side
current imbalance when running at full load. Check
ISM_HIST screen. Check entering condenser
water temperature and water flow rate. Check
MOTOR RATED LOAD AMPS and STARTER
LRA RATING in ISM_CONF screen. VFD applica-
tions only: Any phase current > 120% for exces-
sive time period.
Any LINE CURRENT > MOTOR LOCKED
ROTOR TRIP for excessive time while running
after the LOCKED ROTOR START DELAY has
expired. Check MOTOR LOCKED ROTOR TRIP
and MOTOR CURRENT CT RATIO in ISM_CONF
screen. Check motor nameplate data. Check
ISM_HIST screen. Check motor wiring and motor
winding resistance. Temporarily enable SINGLE
CYCLE DROP OUT to capture power distur-
bances.
Any LINE CURRENT > STARTER LRA RATING.
Check STARTER LRA RATING and MOTOR
CURRENT CT RATIO in ISM_CONF screen.
Check ISM_HIST screen. Check starter label data.
Check motor wiring and motor winding resistance.
Any GROUND FAULT current > GROUND FAULT
CURRENT threshold for a duration > GROUND
FAULT PERSISTENCE after the GROUND
FAULT START DELAY has expired. Check these
settings and GROUND FAULT CT RATIO in
ISM_CONF screen. Check ISM_HIST screen.
Confirm that ground fault current transformer ori-
entation is correct and that the correct motor leads
have been routed through the ground fault current
transformers in the right direction. Check for con-
densation on motor terminals or inside of motor
leads. Check motor power leads for phase to
phase or phase to ground shorts. Disconnect
motor from starter and megger motor windings to
ground and phase to phase. Call Carrier Service.
The ISM has detected that the input power is
phased BAC instead of ABC. Confirm that the
phase sequence wired to ISM terminal block J3 is
consistent with the power wiring to the starter.
Swap two power leads at the starter.
LINE FREQUENCY FAULTING in ISM_CONF
screen is enabled and the LINE FREQUENCY has
deviated approximately 7% from nominal value.
Check ISM_HIST screen. Check FREQUENCY =
60 HZ? In ISM_CONF screen. Check line fre-
quency. If operating from a generator, check gen-
erator size and speed.
Internal ISM power supply is outputting incorrect
voltage. Check ISM status lights. Confirm that 115
V is applied to terminals J1-LL1 and J1-LL2. Con-
firm that excessive voltage has not been improp-
erly applied to any of the ISM terminals before
installing replacement ISM.
The 1M aux contact is open for an excessive time
following a start command and the CONDENSER
PRESSURE < 160 PSI. Check High Pressure
Relay contacts and 115 V wiring leading to ISM
J9-1. Check 115 V wiring leading from ISM J9-2 to
the 1M aux coil and base. Check the 24V circuit
leading from power panel terminal 50 to the 2C
aux contact and High Pressure Switch. Check the
24V circuit leading from power panel terminals 17
and 43 leading to the High Pressure Relay coil and
base.