Trouble Conditions - Honeywell VISTA-32FBPT Installation And Setup Manual

Commercial fire and burglary partitioned security system with scheduling
Hide thumbs Also See for VISTA-32FBPT:
Table of Contents

Advertisement

To enter the Go/No Go Test Mode, proceed as follows:
Step
Action
1
Enter Installer Code + [5].
2
Fault each wireless transmitter, causing each device to transmit.
The keypad will beep three times if the signal is received.
3
If the keypad does not beep, reorient or move the transmitter to another location. Usually a few inches in
either direction is all that is required.
4
Enter Installer Code + OFF to exit the Go/No Go Test Mode.

Trouble Conditions

Supervisory Messages
Display
Description
SUPV +
This indicates that a fire supervisory condition exists on the zone number displayed. This means that the
Zone
operation of the fire alarm system may be compromised.
Number
Check or Trouble Messages
Display
Description
CHECK or
This indicates that a problem exists on the zone number displayed. Zone trouble may be caused by one of
TRBL
the following conditions:
(as per field
A hardwired fire zone is open (broken wire).
3∗ ∗ ∗ ∗ 00)
A Day/Night zone (zone type 5) is faulted.
A polling loop zone is not seen by the control panel.
A polling loop zone has been tampered (cover removed on a 4190SN).
A wireless zone has not checked in during the time programmed in field 1∗31.
A 5800 Series transmitter has been tampered (cover removed).
CHECK 6XX
This indicates a trouble on a 4204CF Supervised Notification Appliance Circuit (corresponding relay number
XX = 01-32
01-32).
CHECK 8XX
This indicates a trouble on a peripheral device (connected to the panel's keypad terminals) of the
XX = 00-30
corresponding device address (00-30).
CHECK 9XX
This indicates that a system trouble exists (RF receiver, Notification Appliance Circuit, etc.).
XX = 70-77,
88,90,97
If the problem has been corrected, enter an OFF sequence (Security Code + OFF) twice to clear the display.
Power Failure
Display
Description
AC LOSS
This indicates that the system is operating on battery power only. Check to see that the circuit breaker for
the branch circuit that your system's transformer is wired to has not been accidentally turned off. Instruct
POWER
the user to call a service representative immediately if AC power cannot be restored.
LED is off
Other System Messages
Display
Description
COMM
Indicates a failure occurred in the telephone communication portion of your system.
FAILURE
LO BAT
Indicates a low-battery condition exists in the wireless transmitter displayed. Pressing any key silences the
audible warning sound.
SYSTEM
This indicates that a low-battery condition exists with the system's backup battery.
LO BAT
HSENS
Indicates a smoke detector with a high sensitivity level, which may cause a false alarm. The detector should
be cleaned or replaced.
72

Hide quick links:

Advertisement

Table of Contents