3.6 Main Alarm data
No.
-
Main alarm data on the bridge shall be acquired and recorded. Check that the data is accurately
acquired.
1
Main and auxiliary steering gear power unit alarm data shall be acquired and recorded. Check that the
data is accurately acquired. Check the output equipment and connection interface condition.
2
Main and auxiliary steering gear control system alarm data shall be acquired and recorded. Check that
the data is accurately acquired. Check the output equipment and connection interface condition.
3
Steering gear, low hydraulic fluid level alarm data shall be acquired and recorded. Check that the data
is accurately acquired. Check the output equipment and connection interface condition.
4
Propulsion machinery remote control system failure data shall be acquired and recorded. Check that
the data is accurately acquired. Check the output equipment and connection interface condition.
5
Propulsion machinery low starting air pressure alarm data shall be acquired and recorded. Check that
the data is accurately acquired. Check the output equipment and connection interface condition.
6
Automatic shutdown of propulsion machinery alarm data shall be acquired and recorded. Check that
the data is accurately acquired. Check the output equipment and connection interface condition.
7
Fault requiring action by or attention of the OOW data shall be acquired and recorded. Check that the
data is accurately acquired. Check the output equipment and connection interface condition.
8
Alarm system normal power supply failure data shall be acquired and recorded. Check that the data is
accurately acquired. Check the output equipment and connection interface condition.
9
Watertight door low hydraulic fluid level alarm data shall be acquired and recorded. Check that the
*b
data is accurately acquired. Check the output equipment and connection interface condition.
10
Watertight door low gas pressure, loss of stored energy alarm data shall be acquired and recorded.
*b
Check that the data is accurately acquired. Check the output equipment and connection interface
condition.
11
Watertight door electrical power loss alarm data shall be acquired and recorded. Check that the data is
*b
accurately acquired. Check the output equipment and connection interface condition.
12
High water alarm data shall be acquired and recorded. Check that the data is accurately acquired.
*b
Check the output equipment and connection interface condition.
13
Shell door position indicator alarm data shall be acquired and recorded. Check that the data is
*b
accurately acquired. Check the output equipment and connection interface condition.
14
Water leakage detection indicator alarm data shall be acquired and recorded. Check that the data is
*b
accurately acquired. Check the output equipment and connection interface condition.
15
Local automatic halon release alarm data shall be acquired and recorded. Check that the data is
*c
accurately acquired. Check the output equipment and connection interface condition.
16
Fire detection in automated or remotely controlled machinery space alarm data shall be acquired and
recorded. Check that the data is accurately acquired. Check the output equipment and connection
interface condition.
17
Fire detection or automatic sprinkler operation alarm data shall be acquired and recorded. Check that
the data is accurately acquired. Check the output equipment and connection interface condition.
18
Smoke detection system power loss alarm data shall be acquired and recorded. Check that the data is
*b
accurately acquired. Check the output equipment and connection interface condition.
19
Smoke detection system alarm data shall be acquired and recorded. Check that the data is accurately
*b*c
acquired. Check the output equipment and connection interface condition.
20
Halon system loss of container alarm data shall be acquired and recorded. Check that the data is
*c
accurately acquired. Check the output equipment and connection interface condition.
21
Halon system electric circuit fault or power loss alarm data shall be acquired and recorded. Check that
*c
the data is accurately acquired. Check the output equipment and connection interface condition.
22
Halon system-hydraulic or pneumatic pressure loss alarm data shall be acquired and recorded. Check
*c
that the data is accurately acquired. Check the output equipment and connection interface condition.
23
Personnel alarm data shall be acquired and recorded. Check that the data is accurately acquired. Check
the output equipment and connection interface condition.
*a
These tables do not include the alarms separately identified for specialist vessels such as gas carriers, fishing vessels,
nuclear ships, high-speed craft or mobile offshore drilling units.
*b
Applicable to vessels constructed on or after February 1992.
*c
These alarms may be omitted if they are provided at the central fire control station.
JCY-1800/1850 VDR/S-VDR Installation Guide
Procedure & Specification
181