12.2 Electrical, EMC and climatic requirements
Comments
Electrostatic air discharge (ESD)
Surge on power supply cables
Surge on data and signal cables
HF irradiation amplitude modulated IEC61000-4-3
HF irradiation, cell phone
frequencies
HF voltage on data, signal and
power supply cables
0.15 to 80 MHz
1)
* An external protection element has to be installed to meet the requirement (e.g.: Blitzductor VT
NOTICE
Radio interference is possible
This is a device of class A. The device may cause radio interference in residential areas.
Implement appropriate measures (e.g.: use in 8MC cabinets) to prevent radio interference.
174
Not applicable for shielded cables and symmetrical ports
AD24V, Dehn&Söhne)
Standard
Severity class
EN 45501
2, 4, 6, 8 kV
OIML R 76
≥ 10 discharges pos/neg
< 10 s repeat time
EN 61000-4-5
1 kV, symmetrical, opt. 1.2 kV
IEC 61131-2
2 kV, asymmetrical, opt. 2.4 kV
NAMUR NE21
1.2/50 µs (8/20) µs pos./neg.
EN 61326
Internal generator resistance: 2 Ω
EN 61000-4-5
1 kV, symmetrical
IEC 61131-2
2kV, asymmetrical, opt. 2.4 kV
NAMUR NE21
1.2/50 µs (8/20) µs
EN 61326
Applies to cables > 30 m
80 to 2 000 MHz: 12 V/m
NAMUR NE21
Mod.: 80% AM with 1 kHz
OIML R76
Note:
EN 45501*3
In the range of 87 to 108 MHz,
174 to 230 MHz and 470 to 790 MHz: 3
V/m
IEC 61000-4-3
900 MHz (± 5 MHz)
1.89 Ghz (± 10 MHz)
10 V/m
Test duration 1 minute
Pulse mod.: 50% sampl. beh.
with 200 Hz
IEC 61000-4-6
10 kHz to 80 MHz: 10 Veff,opt. 12 Veff
NAMUR NE21
Mod.: 80% AM with 1 kHz
EN 61326
OIML R 76
, opt. 1.2 kV
1)
SIWAREX WP241
Manual, 04/2014, A5E33713528A