4.4.2 Flush mounting - ST 700 Standard Transmitter
To mount a flush mounted model, cut a hole for a 1" standard pipe in the tank or pipe where the
transmitter is to be mounted. Weld the 1" mounting sleeve to the wall of the tank or to the hole cut on
the pipe. Insert the meter body of the transmitter into the mounting sleeve and secure with the locking
bolt. Tighten the bolt to a torque of 6,4 Nm +/- 0,30 Nm (4.7 ft-lbs +/- 0.2 ft.-lbs.).
Figure
5 shows a
typical installation for a transmitter with a flush mount on a pipe.
Once the transmitter is mounted, the electronics housing can be rotated to the desired
position. See
for details.
Figure 8
ATTENTION: On insulated tanks, remove enough insulation to accommodate the mounting
sleeve.
Figure 5 - ST 700 Standard Transmitter - Typical Flush Mounted Installation
4.4.3 Mounting Dimensions
Refer to Honeywell drawing number 50049930 (Dual Head), 50049931 (In-Line), 50049932 (Flange
Mount) 50049933 (Extended Flange), 50049934 (Remote Seal) and 50049936 (Flush Mount Pressure
Transmitter) for detailed dimensions. Abbreviated overall dimensions are also shown on the
Specification Sheets for the transmitter models. This section assumes that the mounting dimensions
have already been taken into account and the mounting area can accommodate the Transmitter.
ST 700 SmartLine Pressure Transmitters User's Manual
Page 12
Revision 8.0