14.4 Replacing the Communication Module

The Communication module includes a connector to the sensor ribbon cable and a connector to the
optional Display module. This section includes the procedure to replace the Communication module.
The transmitter does not have to be removed from service to replace the Comm Module
Please take appropriate steps to avoid ESD damage when handling the
Communication and Display Module assemblies
Refer to Figure 63 for parts locations.
Figure 63 – ST 700 Basic Transmitter - PWA Replacement
1. Turn OFF Transmitter power (Power removal is only required in accordance with area
safety approvals. Power removal is only required in Class 1 Div 1 Explosion-proof and
Class 1 Div 2 environments).
When removing the Communications Module with power applied, the loop will go
to 0V. Likewise, installing a Communications Module into a transmitter with power
applied will cause the loop output value to go to 12ma for several seconds then the
loop output value will go to the configured value based on the PV input.
Installing a Display Module into a powered transmitter may cause a temporary upset
to the loop output value.
2.
Loosen the end cap lock, and unscrew the end cap from the electronics side of the
Transmitter housing.
3.
If equipped with a Display module, carefully depress the two tabs on the sides of the
Display Module, and pull it off.
Revision 8.0
ST 700 SmartLine Pressure Transmitters User's Manual
Page 107