Mechanical

Enclosure
• 144 mm (5.7") x 144 mm (5.7") x 146 mm (5.75")
• IP65 / Type 4X / NEMA 4X
• Polycarbonate
Use only approved, suitable size hubs in the enclosure's conduit holes that
Note:
maintain the applicable IP / Type / NEMA rating.
Remote Display Lid
• 144 mm (5.7") x 144 mm (5.7") x 22 mm (0.87")
• IP65 / Type 3 / NEMA 3
• Polycarbonate
• Operational up to 5 m from enclosure base
Blank Lid
• 144 mm (5.7") x 144 mm (5.7") x 22 mm (0.87")
• IP65 / Type 4X / NEMA 4X
• Polycarbonate
WARNINGS:
Ingress protection of the enclosure is reduced to IP20, and Type 4X /
NEMA 4X rating is void when cable entry knock-out in the blank lid is
removed.
An enclosure reduced to an IP20 rating and intended for use in non-
hazardous locations must be installed in an indoor location free of dust
and moisture, or be installed in a suitably rated field enclosure IP54 or
better.
Back Mount Bracket
• 190 mm (7.5") x 190 mm (7.5") x 9 mm (0.35")
• Polycarbonate
Weight
• Enclosure with display lid: 1.3 kg (2.87 lbs)
• Enclosure with blank lid: 1.2 kg (2.65 lbs)

Environmental

Location
• Indoor / outdoor
(only suitable for outdoor use with IP65 / Type 4X / NEMA 4X Enclosure)
Page 252