Siemens SITRANS LUT400 Operating Instructions Manual page 224

Ultrasonic controllers
Hide thumbs Also See for SITRANS LUT400:
Table of Contents

Advertisement

3.4.1.2.
Sets the level for a fixed level simulation, or the starting level for a ramped
simulation.
Values
3.4.1.3.
Enables/disables ramped simulation.
Options
3.4.1.4.
Sets the rate at which the simulated level will change in a ramp simulation.
Options
a.
3.4.2. Discrete Inputs
Simulates behaviour of external contacts connected to a discrete input.
3.4.2.1.
Disables simulation of Discrete Input 1, or sets behaviour of DI during
simulation.
Options
3.4.2.2.
Disables simulation of Discrete Input 2, or sets behaviour of DI during
simulation.
Options
3.4.3. Pump Activations
Sets how physical relays (that are assigned to pumps) will behave in simulation
mode.
Options
Page 216
SITRANS LUT400 (HART) – OPERATING INSTRUCTIONS
Level Value
Range: Low Calibration Point to High Calibration Point
Default: 0.000
Ramp
DISABLED
*
ENABLED
Ramp Rate
SLOW
MEDIUM
*
FAST
Low Calibration Point to High Calibration Point
Discrete Input 1
DISABLED
*
ON
OFF
Discrete Input 2
DISABLED
*
ON
OFF
DISABLED
*
ENABLED
a
1% of span
per second
a
2% of span
per second
a
4% of span
per second
DI is not simulated
DI is simulated to be ON
DI is simulated to be OFF
DI is not simulated
DI is simulated to be ON
DI is simulated to be OFF
Pump relays are not activated in simulation
Pump relays are activated in simulation
A5E33329501