Description; Overview; Features - Siemens SITRANS LUT400 Operating Instructions Manual

Ultrasonic controllers
Hide thumbs Also See for SITRANS LUT400:
Table of Contents

Advertisement

Description

Overview

The Siemens SITRANS LUT400 series controllers are compact, single point, long-range
ultrasonic controllers for continuous level measurement of liquids, slurries, and solids,
and high accuracy monitoring of open channel flow.
The series is compatible with Siemens full line of EchoMax
operating range of 0.3 to 60 meters (dependent on transducer). The SITRANS LUT400 has
been coupled with a backlit Local User Interface (LUI) display featuring menu driven
programming and a host of wizards for plug and play performance. The LUT400 also
features our next generation of Sonic Intelligence
leading measurement performance while improving ease of use. With a number of
advanced pump, alarm, and flow control features, plus a real time clock and an integrated
datalogger, the LUT400 is a powerful and comprehensive solution for your Ultrasonic
applications.

Features

Small 1/2 DIN enclosure footprint with standard universal mounting bracket for wall,
pipe, and DIN rail, plus an optional panel mount
Easy to use LUI display with local four-button programming, menu-driven
parameters, and Wizard support for key applications
Level, Volume, High Accuracy OCM Flow monitoring
Three relays combined with a suite of pump, alarm, and relay control features
HART Communications
EDDs for SIMATIC PDM, AMS Device Manager, and Field Communicator 375/475,
plus DTMs for FDTs (Field Device Tools)
Integrated web browser for local programming from an intuitive web-based
interface
Two discrete inputs for backup level override and pump interlock functions
Echo profile and trend views from the local display
Patented digital receiver for improved performance in electrically noisy applications
(close proximity to VSDs)
Real time clock with daylight savings time supporting an integrated datalogger and
energy saving algorithms for minimizing pump operation during high cost energy
periods
Removable terminal blocks for ease of wiring
A5E33329501
SITRANS LUT400 (HART) – OPERATING INSTRUCTIONS
®
Transducers, allowing an
®
, further strengthening our industry
Page 7