Setting the Data to Output Automatically after Measurements

You can specify the measurement data to output automatically to the PLC after measurements.
Data That Can Be Output
• Data Output
On the FQ2, data that is output after measurement can be assigned to Data 0 to Data 31 in the output data
settings.
When an item is assigned to an output data setting, the data is output in units of four bytes per item.
The maximum data size that can be output at once is 256 bytes.
Note
If multiple inspection results are assigned to one output data setting, that output data setting will be set for more than
four bytes of data output. As a result, it is possible that an item that exceeds the data size (256 byes) that can be out-
put at once will be set in the data output setting. In this case, the output will be divided and output over multiple
cycles.
Output Order of Measurement Data and Output Characters: p. 25
The measurement data from inspection items that can be output and the calculation results from the
expression settings can be output.
For data that can be output, refer to the Measurement Data That Can Be Used for External Outputs and
Calculations for each inspection item.
Assigning Inspection Results to Output Data: p. 153
Assigning More Than One Detection Result to Output Data: p. 154
• Outputting Character Strings
You can output a character string for each of the inspection items that reads a character string, such as the
OCR inspection item. Also, when reading the character string fails, you can output a specific character string
that is set in advance.
Outputting Read Character Strings: p. 156
Assigning Inspection Results to Output Data (Only supported on the FQ2-S4/CH)
You can individually assign the parameters of the inspection items to output data (data 0 to data 31).
The following procedure shows how to assign the measured position X of [0. Search] to data 0 for a binary
output.
[In/Out] − [I/O setting] − [Output data setting] − [Link data output/Fieldbus data output] −
[Output data set]
1
Press [0. Data 0].
2
Press [Data setting].
3
Press [I0. Search].
FQ2-S/CH User's Manual
for Communications Settings
Outputting Data and Controlling Operation through PROFINET
153