3. SPECIFICATIONS
3.1 General specifications
For the general specifications of the AJ65SBT-RPS/RPG module, refer to the
User's Manual of the small remote I/O module.
3.2 Performance specifications
The performance specifications of the AJ65SBT-RPS/RPG are shown below.
Item
Power
supply
Noise immunity
Common
specifications
Dielectric withstand
voltage
Insulation resistance
Weight (kg)
Transmission speed
(bps)
Max. number of
stages connected to
configure segment
(stages)
Max. transmission
CC-Link
distance of each
communication
segment
specifications
Max. number of
modules connected
Number of stations
occupied (stations)
Settable station
number
Connection cable
Applicable connector
Optical
Max. transmission
communication
distance of fiber-
specifications
optic cable between
repeaters (m (ft.))
Voltage (V)
Current
(mA)
Simulator noise of 1500Vp-p
First transient/burst noise IEC801-4: 1kV, obtained by a
noise simulator of 1 s noise width and 25 to 60Hz noise
frequency
500VAC for 1 minute between all DC external terminals
and ground
10M
or higher, measured with a 500VDC insulation
resistance tester
Selectable from among 156k, 625k, 2.5M, 5M and 10M
Varies according to transmission speed. (Refer to the
User's Manual of the applicable master module.)
64 (See Section 2.2 for the conditions for the number of
SI-200/220
500 (1639.34)
7
Specifications
AJ65SBT-RPS
DC20.4 to DC26.4
0.06 (at TYP. 24VDC)
0.2
3
modules connected)
0 (none)
No station numbers
QSI-185/230
CA7003
1000 (3278.69)
AJ65SBT-RPG
2
GI-50/125
CA9103S
2000 (6557.38)