No.
Name
Set the transmission speed of the module (set to 0 at the time of delivery).
Ensure to set the transmission speed at a speed specified below. Unless the
speed is set at a speed specified below, the LED "ERR." will light up.
Setting value
Transmissio
n speed
2)
setting
switch
Set the operating condition of the module (set to OFF at the time of delivery).
3)
Test switch
Terminal
Terminal block for connecting the power supply and CC-Link dedicated
4)
block
cables.
Optical
Terminal block for connecting the CC-Link dedicated cable on the side where
5)
interface
the master station is not located.
Hook for installing the module on the DIN rail.
Hook for
6)
To install the module, press the DIN rail hook at the centerline until you hear it
DIN rail
click.
POINT
The setting of the test switch is made valid when the module power is turned
from OFF to ON. If the setting is changed with the module power ON, perform
the above operation again.
4
0
OFF
1
OFF
2
OFF
3
OFF
4
ON
State of switch
ON
OFF
18
Application
Setting switch status
2
OFF
OFF
ON
ON
OFF
Operating state
Hardware test
Normal operation
Transmission
speed (bps)
1
OFF
156k
ON
625k
OFF
2.5M
ON
5M
OFF
10M