2.2 Cautions on system configuration

(1) Conditions of usable master module
When the AJ61BT11, A1SJ61BT11, AJ61QBT11 and A1SJ61QBT11
modules are used, those of the functional version B or later must be
employed. Use the master module bearing the version 9707 B or later in the
DATE column of the name plate as shown in the figure below.
When the QJ61BT11 module is used, any module can be used irrespective
of the version.
PROGRAMMABLE CONTROLLER
DATE
MITSUBISHI ELECTRIC CORPORATION JAPAN
Year and month
of manufacture
(2) Max. number of modules connected to configure CC-Link system
Remote I/O stations, remote device stations, local stations, ready master
stations, intelligent device stations and repeaters of 64 modules max. can
be connected in one segment.
In the CC-Link system where repeaters are used, also the number of
remote stations capable of being controlled by one master station is the
same as in the other systems.
For details, refer to the User's Manual of the applicable master module.
(3) Combination of optical repeater modules and fiber-optic cable used
Use the optical repeater modules and fiber-optic cable in the following
combination.
Module
AJ65SBT-RPS
AJ65SBT-RPG GI type fiber-optic cable (max. extension distance of cable: 2000m (6557.38ft.))
Example: Combination for use of AJ65SBT-RPG
(AJ65SBT-RPG)
9707
B
BD992D013H01
Function version
SI type fiber-optic cable (max. extension distance of cable: 500m (1639.34ft.))
QSI type fiber-optic cable (max. extension distance of cable: 1000m (3278.69ft))
Repeater
GI type
Fiber-optic cable
MITSUBISHI
CPU UNIT
A2USHCPU-S1
MODEL
MAX 30kSTEP
9707
DATE
MITSUBISHI ELECTRIC
Year and month
of manufacture Function version
Fiber-Optic Cable
Repeater
(AJ65SBT-RPG)
4
B
BD992D008H38

Advertisement

Table of Contents
loading