4.7 Connection of module through cable
The method of connecting the AJ65SBT-RPS/RPG module to the CC-Link
system through the cable is shown below.
Master module
DA
Termination
resistances
DB
DG
SLD
FG
Important
In each segment, ensure to use the same type of CC-Link dedicated cables.
If different types of cables are used, normal data transmission will not be assured.
POINT
• Ensure to connect the terminating resistances to both end modules of each
segment.
In addition, connect them between DA and.
(The terminating resistances are furnished with the module.)
• The terminating resistances vary according to the type of cables in use.
For detail, refer to the User's Manual of the applicable master module.
• Connect the shield cable of the CC-Link dedicated cable to "SLD" of each module,
and ground both ends of the cable through "FG" to a class-D (class 3) ground.
SLD and FG are wired to each other inside the module.
AJ65SBT-RPS/RPG
SLD
CC-Link dedicated
cable
Optical
interface
Optical
interface
Termination
resistances
SLD
AJ65SBT-RPS/RPG
DA
DB
DG
CC-Link dedicated
cable
FG
Fiber-optic cable
DA
DB
DG
CC-Link dedicated
cable
FG
22
Remote module
DA
Termination
resistances
DB
DG
SLD
FG
DA
Termination
resistances
DB
DG
SLD
FG
Local module

Advertisement

Table of Contents
loading

This manual is also suitable for:

Aj65sbt-rpg

Table of Contents