Advertisement

Method of Replacing the Inverter's Power Transistors Modules
Power module checking
When using the digital type of multiple tester, make measurement in diode check mode.
Tester terminal
+
C+
U
V
W
U
V
W
C-
The following abnormalities are also doubted besides the PC board abnormality.
• Faulty compressor (ground fault, ground leakage)
• Faulty fan motor (ground leakage)
236
Criterion
-
U
Not less than 0.3V
(including ∞ )*
V
W
C-
Not less than 0.3V
(including ∞ )*
C+
0.3 to 0.7V
(including ∞ )*
U
0.3 to 0.7V
(including ∞ )*
V
W
*There needs to be none of each value variation.