Daikin ERQ Service Manual page 231

Erq 100/125/140 a7v1b (outdoor unit) ekeqd/f/mcbv3 (control box) ekexv 50/63/80/100/125/140 (expansion valve kit)
Hide thumbs Also See for ERQ:
Table of Contents

Advertisement

ESIE09-05
Troubleshooting
Troubleshooting
Troubleshooting by Indication on the Unified ON/OFF Controller
Be sure to turn off power switch before connect or disconnect connector,
Caution
or parts damage may be occurred.
Has a once
connected optional
YES
controller for centralized
control been disconnected
or itsaddress
changed?
NO
Is the
power supply
NO
turned on for all
optional controllers for
centralized
control?
YES
Is the
reset switch
NO
of all optional controllers
for centralized
control set to
"normal"?
YES
Is
transmission wiring
YES
disconnected or wired
incorrectly?
NO
Is
a central remote
YES
controller or schedule timer
connected?
NO
Are
two or more unified
YES
ON / OFF controllers
connected?
NO
A
Is the
central remote
YES
controller or schedule
timer displaying a
malfunction?
NO
Is the setting
of the unified
NO
ON / OFF controller's
switch for setting
each address
duplicated?
YES
: http://splitoff.ru/tehn-doc.html
Reset power supply
simultaneously for all optional
controllers for centralized
control.
Turn on power supply for
all optional controllers for
centralized control.
Set reset switch to
"normal."
Fix the wiring correctly.
Refer to failure diagnosis for
central remote controller or
schedule timer.
Correct the setting of the
unified ON / OFF controller's
switch for setting each
address and reset the power
supply of the unified ON /
OFF controller.
(V2842)
221

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents