Daikin ERQ Service Manual page 195

Erq 100/125/140 a7v1b (outdoor unit) ekeqd/f/mcbv3 (control box) ekexv 50/63/80/100/125/140 (expansion valve kit)
Hide thumbs Also See for ERQ:
Table of Contents

Advertisement

ESIE09-05
Troubleshooting
Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution
or parts damage may be occurred.
Is the stop
valve open?
1 Mount a pressure gauge on the low-pressure service port.
2 Connect the Service Checker.
3 Reset the operation using the remote controller, and then
restart the operation.
Are the
characteristics of the
low pressure sensor
normal?
(See *1.)
Is the
pressure detected
with the PC board
normal?
(See *2.)
· The low pressure sensor is normal, and the pressure
detected with the PC board is also normal.
· The low pressure has really become low.
Refer to information on P.224, remove the
CHECK 2
causes by which the low pressure has become low.
*1: Make a comparison between the voltage of the pressure sensor (*4) and that read by the
pressure gauge.
(As to the voltage of the pressure sensor, make measurement of voltage at the connector, and
then convert it to pressure according to information on "Pressure Sensor".)
*2: Make a comparison between the low pressure value checked with the Service Checker and the
voltage of the pressure sensor (see *1).
*3: Make measurement of voltage of the pressure sensor.
Micro controller
A/D input
Make measurement of DC voltage between these wires. (*4)
Troubleshooting by Indication on the Remote Controller
NO
YES
NO
YES
NO
YES
+5V
Connector for low pressure sensor
(Blue)
(4)
(3)
(2)
(1)
: http://splitoff.ru/tehn-doc.html
Open the stop valve.
Replace the low pressure sensor.
Replace the main PC board.
Red
Black
Low
pressure
White
sensor
185