Field Setting
b. "Setting mode 2"
Push and hold the MODE (BS1)
button for 5 seconds and set to
"Setting mode 2".
<Selection of setting items>
Push the SET (BS2) button and set
the LED display to a setting item
shown in the table on the right.
Push the RETURN (BS3) button and
decide the item. (The present setting
condition is blinked.)
<Selection of setting conditions>
Push the SET (BS2) button and set
to the setting condition you want.
Push the RETURN (BS3) button and
decide the condition.
Push the RETURN (BS3) button and
set to the initial status of "Setting
mode 2".
∗ If you become unsure of how to
proceed, push the MODE (BS1)
button and return to setting mode 1.
104
No.
Setting item
Cool/heat unified
1
address
Low noise/demand
2
address
Test operation
3
settings
5
AHU forced fan H
AHU forced
6
operation
Defrost changeover
10
setting
External low noise
12
setting / Demand
setting
13 AIRNET address
Additional
20
refrigerant charge
operation setting
Refrigerant
recovery /
21
vacuuming mode
setting
22 Night-time low
noise setting
Setting of external
25
low noise level
Night-time low
26
noise operation
start setting
Night-time low
27
noise operation end
setting
Power transistor
check mode
28
∗Check after
disconnection of
compressor wires
29 Capacity
precedence setting
30 Demand setting 1
32 Normal demand
setting
(V2764)
The numbers in the "No." column represent the number of times to press the
SET (BS2) button.
Description
Sets address for cool/heat unified operation.
Address for low noise/demand operation
Used to conduct test operation without making changes
to the PCB and replacing the refrigerant, after the
completion of maintenance.
Allows forced operation of AHU fan while unit is stopped.
(H tap)
Allows forced operation of AHU.
Changes the temperature condition for defrost and sets to
quick defrost or slow defrost.
Reception of external low noise or demand signal
Set address for AIRNET.
Carries out additional refrigerant charge operation.
Sets to refrigerant recovery or vacuuming mode.
Sets automatic nighttime low noise operation in a simple
way.
The operating time is based on "Starting set" and "Ending
set".
Sets low noise level when the low noise signal is input
from outside.
Sets starting time of nighttime low noise operation.
(Night-time low noise setting is also required.)
Sets ending time of nighttime low noise operation.
(Night-time low noise setting is also required.)
Used for trouble diagnosis of DC compressor. Since the
waveform of inverter is output without wiring to the
compressor, it is convenient to probe whether the trouble
comes from the compressor or PC board.
If the capacity control is required, the low noise control is
automatically released by this setting during carrying out
low noise operation and nighttime low noise operation.
Changes target value of power consumption when
demand control 1 is input.
Normally enables demand control 1 without external
input. (Effective to prevent a problem that circuit breaker
of small capacity is shut down due to large load.)
: http://splitoff.ru/tehn-doc.html
ESIE09-05
Test Operation