Daikin ERQ Service Manual page 111

Erq 100/125/140 a7v1b (outdoor unit) ekeqd/f/mcbv3 (control box) ekexv 50/63/80/100/125/140 (expansion valve kit)
Hide thumbs Also See for ERQ:
Table of Contents

Advertisement

ESIE09-05
Caution
Capacity Setting after changing the main PC Board(A1P) to spare parts PC Board
When you change the main PC Board(A1P) to spare parts PC Board, please carry out the
following setting.
Please Attach the Capacity Setting Adaptor corresponding to Capacity Class (ex. 112, 140, 160) in connector X51A.
(See Below)
Capacity Setting Adaptor
1
2
3
Position of Attaching the Capacity Setting Adaptor
ERQ100 / 125 / 140A7V1B
The following settings are made by pushbutton switches on PC board.
There are the following three setting modes.
Setting mode 1 (H1P off)
Initial status (when normal) : Also indicates during "abnormal".
Setting mode 2 (H1P on)
Used to modify the operating status and to set program addresses, etc. Usually used in
servicing the system.
Monitor mode (H1P blinks)
Used to check the program made in Setting mode 2.
Test Operation
Outdoor unit
Capacity Class
100
112
125
140
140
160
Setting by pushbutton switches
H1P
LED indication
Note
CAPACITY SETTING ADAPTOR (for 100/J112)
CAPACITY SETTING ADAPTOR (for 125/J140)
CAPACITY SETTING ADAPTOR (for 140/J160)
H2P
H3P
H4P
BS1
BS2
BS3
BS4
BS5
MODE
SET
RETURN
TEST
RESET
(V2760)
: http://splitoff.ru/tehn-doc.html
Field Setting
X51A
H5P
H6P
H7P
(Factory setting)