(2) Control Setting for EKEQF-Box
With the EKEQF-box, 2 types of control are possible:
For more information about x-, y-control, refer to "Part 6 Control Box EKEQ - CBV3".
(3) Indoor Fan Control
In cooling and fan only mode, the indoor fan is in ON-mode when the unit is working.
In heating, different situations are possible.
Fan off during thermo off and fan on during defrost/oil return will result in fan on during thermo
off.
(4) Hot Start
During hot start, fan on is carried out when T
Test Operation
x-control: with DDC-controller
y-control: no DDC-controller.
Mode n°
Setting switch n°
23 (13)
0
Mode n°
Setting switch n°
22 (12)
3
23 (13)
8
Mode n°
Setting switch n°
23 (13)
7
6
Setting position n°
01
02
Setting position n°
01
Fan ON at thermo off
02
Fan ON at thermo off
03
Fan OFF at thermo off
01
Fan OFF at defrost and oil return
02
Fan ON at defrost and oil return
03
Fan ON at defrost and oil return
is A°C or after B minutes.
c
Setting position n°
01
A = 34°C
02
A = 37°C
03
A = 40°C
04
A = 43°C
01
B = 0 min
02
B = 1 min
03
B = 3 min
04
B = 5 min
: http://splitoff.ru/tehn-doc.html
Field Setting
Setting
x-control
y-control
Setting
Setting
95