Peripheral Installation
Alarm Sensor Options
Note
Jumper plug P12 on the PIOU is used to set the alarm sensor to detect an open or closed
condition from the facility alarm system.
To detect an open or closed condition by the jumper plug P12
1.
To detect a closed condition, set P12 to the N.O. position.
2.
To detect an open condition, set P12 to the N.C. position.
Jumper W3 on the PIOUS is used to set the alarm sensor to detect an open or closed condition
from the facility alarm system
To detect an open or closed condition by soldering the W3 jumper wire
1.
To detect a closed condition, solder W3 to the normal open position.
2.
To detect an open condition, solder W3 to the normal closed position.
Alarm Sensor Wiring
Refer to
PIOUS PCB.
PIOU PCB
N.C.
Alarm
P12
Sensor
N.O.
PIOUS PCB
Normal Open
Alarm
Sensor
Normal Close
Figure 6-26 DK40 Alarm Sensor Block Diagram (PIOU/PIOUS)

Auto Attendant

Auto Attendant operates like an automatic station attendant or switchboard operator that
quickly and efficiently distributes calls to stations selected by callers. Incoming calls are
greeted by an external announcement device that offers callers a menu of station locations
6-50
Refer to the Strata DK40 Programming Manual or DK Library CD-Rom for more details.
Refer to
Figure 6-26
Figure
6-26, and connect the facility alarm system relay contacts to the PIOU/
PIOU Pin Numbers ( )
25-Pair Cable
ALMT (36)
ALMR (11)
ALMT
W3
ALMR
for additional information.
25-Pair Cable
Twisted
Pair
TB1
ALM
MDF
MDF
Strata DK40 I&M Manual Spring 1999
Auto Attendant
Facility
Alarm
System
Facility
Alarm
System
1541