Condition
BATTERY
SELF TEST
NORMAL
REPLACE
Resetting the UPS
To reset the UPS while an alarm condition is present, press the
Output On button until the UPS alarm beeps.
Silencing the Alarm
To silence the alarm for an existing fault, press and hold the
Output On button for one second. The alarm becomes quiet.
If UPS status changes, the alarm beeps, overriding previous alarm
silencing. Press the Output On button again to silence the alarm.
Powerware
®
Prestige Series Installation and Operator's Manual for IBM Applications (6000 VA) Uncontrolled Copy
Possible Cause
Weak battery while in Bypass
mode.
Self Test failure. UPS internal
problem.
Weak battery.
Action
This usually indicates that the batteries
need replacing or the UPS requires
service. Contact your service
representative.
The UPS may switch to Bypass mode,
depending on the circumstances.
Reset the UPS by pressing the
Output
On button until the alarm
|
beeps.
Contact your service representative if
condition persists.
Verify that the battery is connected and
the battery circuit breaker is in the
ON (
) position. If battery is properly
|
connected, allow the battery to charge
for 24 hours. Retest. Have batteries
replaced if condition persists.
Troubleshooting
73