Resetting The Ups; Silencing The Alarm - Powerware Prestige series 9 User Manual

600 va - 1800 va
Hide thumbs Also See for Prestige series 9:
Table of Contents

Advertisement

Condition
OVERTEMP
BATTERY
BATTERY
BATTERY
SELF TEST

Resetting the UPS

To reset the UPS while an alarm condition is present, press the
Output On button until the UPS alarm beeps.

Silencing the Alarm

To silence the alarm for an existing fault, press and hold the
Output On button for one second. The alarm becomes quiet.
If UPS status changes, the alarm beeps, overriding previous alarm
silencing. Press the Output On button again to silence the alarm.
Powerware
9 Prestige Series User's Guide (600 VA - 1800 VA)
®
Possible Cause
UPS internal temperature is too
high. The alarm beeps and the
UPS switches to Bypass mode
for approximately 10 minutes,
allowing the UPS to cool down.
Weak battery while in Normal
mode. The alarm beeps.
Battery breaker is open (O).
Battery cabinet is not properly
connected to the UPS.
Weak battery while in Bypass
mode.
Self Test failure. UPS internal
problem.
:
www.powerware.com
Action
Shut down the UPS. Clear vents. Remove
any heat sources. Wait approximately
5 minutes and retry.
Contact your service representative if
condition persists.
Allow the battery to charge for 24 hours,
then retest. Have batteries replaced if
condition persists.
Verify that the battery circuit breaker is in
the ON (
) position.
|
Verify that the battery cords are
connected.
This usually indicates that the batteries
need replacing or the UPS requires service.
Contact your service representative.
The UPS may switch to Bypass mode,
depending on the circumstances.
Reset the UPS by pressing the Output
button until the alarm beeps.
Contact your service representative if
condition persists.
Troubleshooting
On
|
59