Bios Update - Siemens simatic ET 200SP User Manual

Open controller
Hide thumbs Also See for simatic ET 200SP:
Table of Contents

Advertisement

Functions
8.3 BIOS description
Menu
Exit
8.3.5

BIOS update

With the SIMATIC IPC DiagBase software (included in scope of delivery), you can perform
the following actions:
● Perform a BIOS update.
● Saving and updating the current BIOS version.
● Saving the BIOS settings or loading them from another backup.
For additional information, refer to the online help for the SIMATIC IPC DiagBase software.
Requirements
● The S7-1500 software controller CPU 1505S must be in STOP mode.
● The CPU 1515SP PC must be started in Windows mode.
NOTICE
Malfunctions in the software controllers due to critical actions
If a BIOS update is performed during CPU 1505S operation, malfunctions may occur in the
software controller, such as communication breakdowns and failures.
During operation of the CPU 1505S, do not perform a BIOS update or other actions that
place an extremely high demand on the hardware.
Before a BIOS update, switch the CPU 1505S to STOP.
64
System parameters
Exit Saving Change
Save Change Without Exit
Exit Discarding Changes
Load Optimal Defaults
Load Custom Defaults
Safe Custom Defaults
Discard Changes
Default settings
Standard
User settings
CPU 1515SP PC
Manual, 12/2014, A5E32701806-AA