Technical data
10.1 Standards and approvals
Marine approval (available soon)
Classification societies:
● ABS (American Bureau of Shipping)
● BV (Bureau Veritas)
● DNV (Det Norske Veritas)
● GL (Germanischer Lloyd)
● LRS (Lloyds Register of Shipping)
● Class NK (Nippon Kaiji Kyokai)
Use in industrial environments
SIMATIC products are designed for use in industry.
Table 10- 1
Area of applica-
tion
Industry
Use in residential areas
Note
The ET 200SP is intended for use in industrial areas; use in residential areas may have an
impact on radio/TV reception.
If you want to use the ET 200SP in residential areas, you must ensure that its radio
frequency interference emission complies with limit class B in accordance with EN 55011.
Suitable measures for achieving RF interference level Class B include, for example:
● Installation of the CPU 1515SP PC in grounded control cabinets/control boxes
● Use of filters in the supply lines
Reference
The certificates for the markings and approvals can be found on the Internet under
Service&Support (http://www.siemens.com/automation/service&support).
86
Use in industrial environments
Interference emission requirements
EN 61000-6-4: 2011
Interference immunity requirements
EN 61000-6-2: 2005