10.3
Shipping and storage conditions
Introduction
With respect to shipping and storage conditions, the CPU 1515SP PC exceeds the
requirements according to IEC 61131-2. The following statements apply to modules that are
transported and/or stored in the original packaging.
Table 10- 7
Type of condition
Free fall (in shipping package)
Temperature
Barometric pressure
Relative humidity
Sinusoidal vibrations according to
IEC 60068-2-6
Shock according to IEC 60068-2-27
10.4
Mechanical and climatic ambient conditions
Note
Restrictions
In contrast to the ambient conditions for the ET 200SP distributed I/O system, the following
restrictions apply to the CPU 1515SP PC:
• Mechanical ambient conditions:
– 2 g constant acceleration when BusAdapter BA 2×FC is used
• Ambient temperature:
– 0 to 60 °C for horizontal installation with maximum 32 I/O modules
– 0 to 55 °C for horizontal installation with maximum 64 I/O modules
– 0 to 50 °C for vertical installation with maximum 32 I/O modules
Operating conditions
The CPU 1515SP PC is suitable for use in weather-proof, fixed locations. The operating
conditions exceed the requirements according to DIN IEC 60721-3-3:
● Class 3M3 (mechanical requirements)
● Class 3K3 (climatic requirements)
CPU 1515SP PC
Manual, 12/2014, A5E32701806-AA
Shipping and storage conditions for modules
10.3 Shipping and storage conditions
Permissible range
≤1 m
From -40 °C to +70 °C
1080 hPa to 660 hPa (corresponds to an altitude of
-1000 m to 3500 m)
5% to 95%, without condensation
5 - 8.4 Hz: 3.5 mm
8.4 - 500 Hz: 9.8 m/s
2
250 m/s
, 6 ms, 1000 shocks
2
Technical data