Fan; Cooling The Simotion D410-2; Overview Of Fan States - Siemens SIMOTION D410-2DP/PN Installation Manual

Table of Contents

Advertisement

5.7

Fan

5.7.1

Cooling the SIMOTION D410-2

Overview
A fan is always required for operation of the SIMOTION D410-2. This is included in the scope
of delivery of the D410-2 control unit. The fan operates temperature-controlled and is switched
on depending on the air intake temperature and the CPU load.
Fan faults
Fan faults are indicated as follows:
● Entry in diagnostic buffer
● Indicated via system variable
● Calling the PeripheralFaultTask
If a fan fault occurs or the fan is unplugged, the module continues to run. The controller goes
into FAULT state when overtemperature occurs (temperature threshold 2 exceeded), whereby
all LEDs flicker red. The state can only exited through power off/on
For further information on the evaluation of fan faults, see Section Overview of fan states
(Page 99).
5.7.2

Overview of fan states

Evaluation of fan faults
SIMOTION D410-2 has a single fan.
Fan faults are detected through a cyclic fan test or when a malfunction is determined when
the fan is activated (fan does not rotate or fan rotates at too low a speed).
Fan faults are signaled by the following diagnostic buffer entry:
Fan on the module is defective.
SIMOTION D410-2
Commissioning and Hardware Installation Manual, 01/2015
Commissioning (hardware)
5.7 Fan
99