Factory Settings - Siemens RDF870KN Series Manual

Touch screen flush-mounted pm2.5 & iaq controllers with knx or rs485 modbus
Hide thumbs Also See for RDF870KN Series:
Table of Contents

Advertisement

Firmware setpoint settings
Item
Description
TCSP
Filter time setting
PM2.5 SP
PM2.5 setpoint
CO2 SP
CO
setpoint
2
T SP
Temperature setpoint
T SP H
Temperature setpoint range high
T SP L
Temperature setpoint range low
VOC SP
VOC setpoint
HUM SP
Humidity setpoint
1)
P81
Device address (KNX only)
1)
P81 is only for ETS and local HMI does not support P81:
During powering up, there is a startup delay (TwaitDevice = tWaitMin + DeviceAdr * 200ms) before the pro-
cessing signal is processed.
When P81=255 (default), the device does not process the signal according to heartbeat and COV mecha-
nism. But it can respond when another device is polling.
The local HMI does not support P81.
When individual address is changed via ETS, P81 is updated automatically after device downloads it from
ETS.
22
Siemens
Smart Infrastructure
Range
0...9999
SPML...SPMH
SPCL...SPCH
T SP L...T SP H
Max. of low range...200 (°C)
-50...Min. of high range (°C)
%: 0...100
mg/m
3
: 0...5
0...100 %
1...255

Factory settings

8760
60
1000
24
50
5
3
0.6 mg/m
or 6 %
50 %
255
A6V11439454_en--_d
2021-03-31