Preparation
• Start signal ...................................Switch, relay, etc. (for 1)
• Frequency setting signal ..............0 to 5V, 0 to 10V or 4 to 20mA DC signals from a potentiometer or outside
• Operation unit...............................Operation panel (FR-DU04), parameter unit (FR-PU04)
• Connection cable .........................To be prepared for use of the operation unit away from the inverter
3) Combined operation mode
Change the setting of Pr. 79 "operation mode selection" as follows:
Setting
Running frequency setting
PU (FR-DU04/FR-PU04)
• Direct setting and
3
Multi-speed setting
Terminal signal
• 0 to 5VDC across 2-5
• 0 to 10VDC across 2-5
• 4 to 20mADC across 4-5
4
• Multi-speed selection (Pr. 4 to Pr. 6, Pr. 24
to Pr. 27)
• Jog frequency (Pr. 15)
( 4 ) Communication operation mode
Communication operation can be performed by connecting a personal computer and the PU connector with
the RS-485 communication cable.
The inverter setup software (FR-SW"-SETUP-WE (or –WJ for Japanese Version)) is available as a startup
support software package for the FR-F500.
Preparation
• Connection cable .........................Connectors and cables available on the market
For the operation environment of inverter setup software, refer to the instruction manual of the inverter setup
software.
the inverter (for 2)
FR-CB2"" (option) or the following connector and cable available on the
market:
• Connector: RJ45 connector
• Cable
: Cable conforming to EIA568 (e.g. 10BASE-T cable)
Description
Terminal signal
• STF
key setting,
• STR
Parameter unit
key
FWD
key
REV
• Connector : RJ45 connector
• Cable
: Cable conforming to EIA568
(E.g. 10BASE-T cable)
46
OPERATION/CONTROL
Start signal