Transistorized inverter
Hide thumbs Also See for FR-F500 Series:
Table of Contents

Advertisement

<Setting>
Refer to the following list and set the parameters:
Signal
Setting
Name
Pr. 59 = 0
0
RL
Pr. 59 = 1, 2*
Pr. 59 = 0
1
RM
Pr. 59 = 1, 2*
Pr. 59 = 0
2
RH
Pr. 59 = 1, 2*
3
RT
Second function selection
4
AU
Current input selection
5
JOG
Jog operation selection
6
CS
Automatic restart after instantaneous power failure selection
External thermal relay input**
The externally provided overheat protection thermal relay,
7
OH
motor-embedded temperature relay, etc is operated to stop
the inverter.
10
X10
FR-HC, FR-CV connection (inverter operation enable)
FR-HC connection (instantaneous power failure detection)
11
X11
(Only when FR-A5NR option is fitted)
12
X12
PU operation external interlock
13
X13
External DC injection brak start
14
X14
PID control valid terminal
16
X16
PU-external operation switch-over
PID forward-reverse action switching function
24
X24
(NA, EC versions only)
9999
No function
*: When Pr. 59 = "1" or "2", the functions of the RL, RM, RH and RT signals change as listed above.
**: Operated when the relay contact "opens".
Note: 1. One function can be assigned to two or more terminals. In this case, the terminal inputs are
OR'ed.
2. The speed command priorities are higher in order of jog, multi-speed setting (RH, RM, RL) and
AU.
3. When the X10 signal (inverter operation enable signal for FR-HC, FR-CV connection) is not set,
the MRS terminal shares this function.
4. Use common terminals to assign the multi-speeds (7 speeds) and remote setting. They cannot
be set individually.
(Common terminals are used since these functions are designed for speed setting and need not
be set at the same time.)
5. When "7" is set in Pr. 79 and the PU operation external interlock (X12) signal is not assigned, the
MRS signal acts as this function.
Functions
Low-speed operation command
Remote setting (setting clear)
Middle-speed operation command
Remote setting (deceleration)
High-speed operation command
Remote setting (acceleration)
141
PARAMETERS
Relevant Parameters
Pr. 4 to Pr. 6
Pr. 24 to Pr. 27
Pr. 232 to Pr. 239
Pr. 59
Pr. 4 to Pr. 6, Pr. 24 to Pr. 27, Pr. 232 to
Pr. 239
Pr. 59
Pr. 4 to Pr. 6, Pr. 24 to Pr. 27,
Pr. 232 to Pr. 239
Pr. 59
Pr. 44 to Pr. 50
Refer to page 10
Pr. 15, Pr. 16
Pr. 57, Pr. 58, Pr. 162 to Pr. 165
Refer to page 166
Pr. 30
Pr. 30
Pr. 79
Pr. 10 to Pr. 12
Pr. 128 to Pr. 134
Pr. 79
Pr. 500 to Pr. 516
4