Mitsubishi Electric FR-F500 Series Instruction Manual page 165

Transistorized inverter
Hide thumbs Also See for FR-F500 Series:
Table of Contents

Advertisement

# Assign the motor control signals (SLEEP, R01 to R04, RI01 to RI04) to Pr. 190 to Pr. 195 (output terminal
function selection) or assign them to Pr. 320 to Pr. 322 (RA1, RA21, RA3 output selection) using the
inboard option (FR-A5AR). (The functions of the output terminals are positive logic only.) (Refer to page
142)
Parameter Number
190
RUN terminal function selection
191
SU terminal function selection
192
IPF terminal function selection
193
OL terminal function selection
194
FU terminal function selection
320
RA1 output selection (valid only when the FR-A5AR is used)
321
RA2 output selection (valid only when the FR-A5AR is used)
322
RA3 output selection (valid only when the FR-A5AR is used)
Setting Range
40, 41, 42, 43, 44, 45,
46, 47, 48
Name
Set value
Signal name
40
SLEEP
41
R01
42
R02
43
R03
44
R04
45
RI01
46
RI02
47
RI03
48
RI04
Description
Function
Output at stop
Commercial power supply side motor 1 connection R01
Commercial power supply side motor 2 connection R02
Commercial power supply side motor 3 connection R03
Commercial power supply side motor 4 connection R04
Inverter side motor 1 connection RI01
Inverter side motor 2 connection RI02
Inverter side motor 3 connection RI03
Inverter side motor 4 connection RI04
152
PARAMETERS