Mitsubishi Electric FR-F500 Series Instruction Manual page 205

Transistorized inverter
Hide thumbs Also See for FR-F500 Series:
Table of Contents

Advertisement

Operating
PU (FR-DU04
status
/FR-PU04)
Alarm
definition
Operating
Additional
status
display on
Alarm
parameter unit
definition
(FR-PU04)
Interactive
only
guidance
Protective/alarm functions
Ambient temperature
Ambient humidity
Storage temperature
(Note 2)
Ambience
Altitude, vibration
Note: 1. Jog operation may also be performed from the operation panel or parameter unit.
2. Temperature applicable for a short period in transit, etc.
Selection can be made from output frequency, motor current (steady or peak value), output
voltage, frequency setting, running speed, overload, converter output voltage (steady or peak
value), electronic overcurrent protection load factor, input power, output power, load meter,
total energization time, actual operation time, total power and motor load factor.
Alarm definition is displayed when protective function is activated. 8 alarm definitions are stored.
(Four alarm definitions are only displayed on the operation panel.)
Input terminal signal states, output terminal signal states, option fitting status, terminal
assignment status
Output voltage/current/frequency/cumulative ON time immediately before activation of
protective function
Operation guide and troubleshooting by help function
Overcurrent shut-off (during acceleration, deceleration, constant speed), regenerative
overvoltage shut-off, undervoltage, instantaneous power failure, overload shut-off (electronic
overcurrent protection), ground fault current, output short circuit, main circuit device overheat,
stall prevention, overload alarm, heatsink overheat, fan fault, option fault, parameter error, PU
disconnection, retry count exceeded, output phase failure, CPU error, 24VDC power output
short circuit, operation panel power supply short circuit
-10°C to +50°C (14°F to 122°F) (non-freezing)
(-10°C to +40°C (14°F to 104°F) for totally enclosed structure specification attachment FR-
A5CV)
90%RH or less (non-condensing)
-20°C to +65°C (-4°F to +149°F)
Indoors. (No corrosive and flammable gases, oil mist, dust and dirt.)
Maximum 1000m (3280.80feet) above sea level for standard operation.
After that derate by 3% for every extra 500m (1640.40feet) up to 2500m (8202.00feet) (91%).
2
5.9 m/s
or less (conforming to JIS C 0040)
190
SPECIFICATIONS
6

Advertisement

Table of Contents
loading

Table of Contents