( 3 ) Changing the control logic
The input signals are set to sink logic for the Japanese and NA version, and to source logic for the EC
version.
To change the control logic, the connector on the back of the control circuit terminal block must be moved to
the other position.
(The output signals may be used in either the sink or source logic independently of the jumper connector
position.)
1) Loosen the two mounting screws in both ends of the control circuit terminal block. (The screws cannot be
removed.)
Pull down the terminal block from the back of the control circuit terminals.
2) Remove the jumper connector from the rear surface of the control circuit terminal block and place in
required Logic position (either Sink or Source).
EC version
3) Using care not to bend the pins of the control circuit connector, reinstall the control circuit terminal block
and fix it with the mounting screws.
Note: 1. Make sure that the control circuit connector is fitted correctly.
2. While power is on, never disconnect the control circuit terminal block.
3. The sink-source logic change-over jumper connector must be fitted in only one of those
positions. If it is fitted in both positions at the same time, the inverter may be damaged.
NA and Japanese version
INSTALLATION AND WIRING
19