Fan Motor (Dc Motor) Or Related Abnormality - Daikin FVKS25BVMB Service Manual

Inverter pair floor standing type b series
Hide thumbs Also See for FVKS25BVMB:
Table of Contents

Advertisement

Si06-305
4.4
Fan Motor (DC Motor)
A6
Remote
Controller
Display
Method of
The rotation speed detected by the hall IC during fan motor operation is used to determine
Malfunction
abnormal fan motor operation.
Detection
Malfunction
When the detected rotation speed is less than 50% of the H tap under maximum fan motor
rotation demand.
Decision
Conditions
Supposed
Causes
Service Diagnosis
Operation halt due to short circuit inside the fan motor winding.
Operation halt due to breaking of wire inside the fan motor.
Operation halt due to breaking of the fan motor lead wires.
Operation halt due to faulty capacitor of the fan motor.
Detection error due to faulty indoor unit PCB (1).
or Related Abnormality
Troubleshooting