Control Specification
3.6

Freeze-up Protection Control

Outline
During cooling operation, the signals being sent from the indoor unit allow the operating
frequency limitation and then prevent freezing of the indoor heat exchanger. (The signal from
the indoor unit must be divided into the zones as the followings.
Detail
Conditions for Start Controlling
Judge the controlling start with the indoor heat exchanger temperature after 2 sec from
operation start.
Control in Each Zone
3.7

Heating Peak-cut Control

Outline
Heat Pump Only
During heating operation, the signals being sent from the indoor unit allow the operating
frequency limitation and prevent abnormal high pressure. (The signal from the indoor unit must
be divided as follows.)
Detail
Conditions for Start Controlling
Judge the controlling start with the indoor heat exchanger temperature after 2 min from
operation start.
Control in Each Zone
The heat exchange intermediate temperature of indoor unit controls the following.
34
Si06-305
Function and Control