Indoor Fan Motor (DC Motor) or Related Abnormality
A6
Error Code
Method of Error
The rotation speed detected by the Hall IC during indoor fan motor operation determines abnormal
Detection
fan motor operation.
Error Decision
The detected rotation speed does not reach the demanded rotation speed of the target tap, and is
Conditions
less than 50% of the maximum fan motor rotation speed.
Supposed
Remarkable decrease in power supply voltage
Causes
Layer short inside the fan motor winding
Breaking of wire inside the fan motor
Breaking of the fan motor lead wires
Defective capacitor of the fan motor
Defective indoor unit PCB
Troubleshooting
FTX09/12/15NMVJU
Part 6 Service Diagnosis
Be sure to turn off the power switch before connecting or disconnecting
Caution
connectors, or parts may be damaged.
Turn off the power supply.
(Unplug the power cable or turn
the breaker off.)
Check the connector for
connection.
OK?
YES
Foreign matters in or
around the fan?
NO
Rotate the fan by hand.
A
Go to the next page
Note: The motor may break when the
motor connector is disconnected
with the power supply on.
(Turn off the power supply before
connecting the connector also.)
∗ To secure the connection,
once disconnect the connector
and then reconnect it.
NO
YES
Troubleshooting for FTX, FVXS Series
Correct the connection.
Remove the foreign matters.
(R23939)