Fan Motor (Dc Motor) Or Related Abnormality - Daikin D Series Service Manual

Inverter pair wall mounted type, cooling only, heat pump
Hide thumbs Also See for D Series:
Table of Contents

Advertisement

SiEBE04-507
4.4

Fan Motor (DC Motor) or Related Abnormality

A6
Remote
Controller
Display
Method of
The rotation speed detected by the Hall IC during fan motor operation is used to determine
Malfunction
abnormal fan motor operation.
Detection
Malfunction
When the detected rotation speed is less than 50% of the H tap under maximum fan motor
rotation demand.
Decision
Conditions
Supposed
Causes
Service Diagnosis
Operation halt due to short circuit inside the fan motor winding.
Operation halt due to breaking of wire inside the fan motor.
Operation halt due to breaking of the fan motor lead wires.
Operation halt due to faulty capacitor of the fan motor.
Detection error due to faulty indoor unit PCB.
Troubleshooting