Si06-305
1.9

Inverter Powerful Operation

Outline
In order to exploit the cooling and heating capacity to full extent, operate the air conditioner by
increasing the indoor fan rotating speed and the compressor frequency.
Details of the
When Powerful button is pushed in each operation mode, the fan speed / setting temperature
will be converted to the following states in a period of twenty minutes.
Control
Operation mode
Cooling
Dry
Heating
Fan
Automatic
Ex.) : Powerful operation in cooling mode.
Target temp.
Set temp.
18˚C
Powerful ON
Powerful OFF
Fan
H tap
Set tap
Function and Control
Fan speed
H tap + 70 rpm
Dry rotating speed +
50 rpm
H tap + 80 rpm
H tap + 70 rpm
Same as cooling /
heating in Powerful
operation
It should be the lower limit of cooling temperature.
80rpm
TPF=(20min.)
Target set temperature
18°C
Normally targeted
temperature in dry
operation; Approx. - 2°C
30°C
The target is kept
unchanged
It counts 20 min. also in the remote controller.
Ending condition: "or" in 1 to 3
1. TPF ends.
2. Stop
3. Powerful operation is OFF.
Main Functions
(R2823)
23